Information

  • Document No.00031/03/2016

  • Site

  • Date

  • Auditor

  • Location
  • Personel

  • The temperature of blended water outlets must be distributed in the range of 41 and 43 Degrees Celsius
    The temperature of cold water outlets must be distributed at or below 20 Degrees Celsius
    The temperature of hot water outlets must be distributed at or above 50 Degrees Celsius

    1. Run the outlet for 1 minute on hot and blended water outlets, cold water outlets run water for 2 minutes
    2. Test the temperature with a thermometer
    3. Record the temperature in the following audit by stating Safe/At Risk and add the reading into the text box

Cold water tap temperatures of 20c after 2 minutes running. Minimum hot water temperature of 50c after 1 minute running.

  • Outlet 1<br>

  • Outlet 2

  • Outlet 3

  • Outlet 4

  • Outlet 5

  • Outlet 6

  • Outlet 7

  • Outlet 8

  • Outlet 9

  • Outlet 10

  • Outlet 11

  • Outlet 12

Signature

  • Competent Person

  • Technical manager

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.