Title Page
-
Site conducted
-
Conducted on
-
Prepared by
-
Location
-
Position of insulated panel
-
Core Material
- EPS - Expanded Polystyrene
- XFlam or other Fire Rated
- Other
-
Provide details
-
FM Class 1
-
Core Thickness (mm)
-
Floor Area (%)
-
Surface Area (%)
-
Max Wall Height (m)
-
Usage
- Cold Storage
- Freezer Unit
- Cold storage/freezer unit
- Insulation - external walls
- Insulation - internal walls
- Insulation - internal/external
- Compartment for production
- Other
-
Provide detail
-
Condition
-
Hot/Cold Work Procedure
-
Regular Self-Inspections
-
Panel faces along all sections are in good condition with no exposed core material
-
All electrical cabling/wiring is fully enclosed within approved plastic or metal conduit with appropriate seals/flashing/capping where it passes through insulated panels
-
All flues have appropriate clearances and flashing/capping through insulated panels
-
Diffusers (covers) are fitted to all light bulbs/lamps so that any failure of a bulb/lamp, or its associated ballast, will not result in heated components potentially falling onto combustible items stored below
-
Where insulated panels form external wall sections of a building, combustible items and/or rubbish bins are not stored within 6m of these external panels
-
All heat sources are kept at least 2 metres from any insulated panels
-
Battery chargers are positioned 2 metres from any insulated panels or non-combustible material such as Fyrchek or checkerplate has been installed between the chargers and the insulated panels