Information

Project Details (Completion of all of the following fields is mandatory. Forms submitted without all fields completed will not be assessed.)

  • Audit Title/Project Description

  • Design Pack ECB Link ID (eg. ABC-1234)

  • Work Parcel/Contract No.

  • Separable Portion No.

  • Order No.

  • Site Address
  • Project Manager

  • Team Manager

  • Authority Number

  • Installer Name

  • Installation Date

Section 1

Rack OMS1460

  • a. No damage to rack (structural /paint /plating)

  • b. Correct Earth tree fitted

  • c. Scratches, exposed rivets covered with supplied patches

  • d. Rack installed in the correct floor position

  • e. Rack installed at the same s/structure height as adjacent racks

  • f. Rack level and plumb (check with spirit level)

  • g. Rack securely attached to superstructure or wall using correct mounting kits and isolation practices

  • h. High superstructure kit “thick washers installed below RH C-channel”.

  • i. Rack securely fixed to floor, using supplied anchors & feet set at 45 degree angle to frame edges

  • j. Rack correctly located over floor tiles (raised floor only)

  • Ref: Design Pack,TM00046

  • *Mandatory photo required - Rack photos showing rack at installation.

Section 2

APDP

  • a. Anderson connectors for each rack primary feed RF1 & RF2 cable tied to prevent accidental pulling apart

  • b. Correct alarm cable and colour code

  • c. Alarm cables terminated correctly on Krone Terminations

  • d. Alarm priority switches set to correct position

  • e No Excessive Cable Lengths APDP

  • f. No permanent alarms on APDP

  • Ref: TM00046 A01

  • *Mandatory photo required - Close-up of APDP showing power terminations & CB’s

Section 3

Rack Primary Power Feed Cables

  • a. Rack power cables correct size

  • b. Rack power cables segregated from the LOD Primary Power 150 mm2 cables

  • c. Rack power cables contained within the power tray

  • d. Cables not damaged/ against a sharp edge

  • e. Rack feed A& B fed from different subracks / planes but same CB position (unless specified in Design Pack)

  • f. Power cable lugs / ferrels crimped correctly / securely at LOD

  • g. Heatshrink on all lugs

  • h. LOD CBs correct type and rating

  • i. LOD CB Locking clip is in the “closed” position

  • Ref: TM00046 A01, CSD 26204


  • *Mandatory photo required - Photo of primary connections at distribution point

Section 4

OMS1410 Subrack

  • a. Subrack installed in correct position as per rack layout

  • b. Power cables run correctly

  • Ref: TAF0001-115198

  • *Mandatory photo required - Photo of subrack showing Power cables ,2 Meg copper, fibre etc.

Section 5

OMS1410 Subrack Mounting Brackets

  • a. Subrack mounting brackets correctly installed and secure

  • Ref: TAF0001-118783

  • *Mandatory photo required - Close up picture of the mounting brackets to confirm that installed correctly.

Section 6

Couplers SFW

  • a. Maximum of 8 SFW couplers installed per tray

  • b. SFW couplers installed in the rear 8 positions of comb<br>

  • c. Fibres to/from the SFW couplers run to the front of tray & form a 1800 bend either clockwise or anticlockwise around the coupler as required to exit the tray

  • d. Thru connector for single fibre side of the coupler is positioned on the opposite side of the coupler entry/ exit point

  • e. SFW Trays correctly modified

  • f. SFW Trays Labelled with “THIS TRAY RESERVED FOR SFW COUPLERS (MAX 8 PER TRAY)”

  • Ref: TAF0001-118783

  • Insert photos please

Section 7

2Mbit Twisted Pair Cabling OMS1410 Subrack End

  • a. Twisted Pair cabling routing correct, neatly run & secured

  • Ref: TAF0001-115198

  • Insert photo please

Section 8

2Mbit Twisted Pair Cabling DDF End

  • a. EQ IN and OUT cables not tied together on long runs

  • b. Cables run and secured correctly down DDF (within guides)

  • c. Cable bending radius not violated

  • d. Correct gooseneck into blocks

  • e. Cable butted correctly at grommet

  • f. Cables not damaged/ against a sharp edge

  • Ref: TM 00099 A01

  • Insert photo please

Section 9

2Mbt DDF Blocks

  • a. Grommets correctly fitted

  • b. Jumper rings fitted & secure

  • c. Back mounts fitted correctly

  • d. Back mounts installed with full compliment of modules

  • e. Label holders fitted to modules

  • f. Wires lay over modules correctly

  • g. Correct wiring, colour code etc

  • h. 100mm tail left behind modules

  • i. Jumpers routed correctly

  • Ref: TM 00099 A01

  • Insert photos please

Section 10

Labelling Rack Header OMS1410

  • a. Rack labelled with rack header label

  • b. Rack labelled with SRPP label

  • Ref: TAF0001-115198

  • *Mandatory photo required - Photo of Rack Header showing both labels

Section 11

Labelling APDP

  • a. APDP Subrack label correct size

  • b. Subrack Position correct format

  • c. RF1 & RF2 , Fuse / Breaker Location correct format

  • d. Circuit Breaker designation for relevant subracks

  • e. Correct ACCADS/TESAMS alarm IDF location

  • *Mandatory photo required - Photo of APDP label, use Macro setting

Section 12

Ericsson Specific Labelling (Supplied Labels)

  • a. Subrack label placed in correct position and contains LIS & NE-ID

  • b. Wrap around labels are orientated so that the text reads away from the connector

  • Ref: TAF0001-655524

  • Please insert photos.

Section 13

Labelling Optical Fibres

  • a. Multiple port card connectors labelled with SLOT & Port number IN or OUT

  • b. Single port cards labelled with SLOT & Port IN or OUT

  • c. Wrap around labels used NO LABEL FLAGS<br>

  • d. Wrap around labels are orientated so that the text reads away from the connector

  • e.Both ends of fibre pigtail labelled<br>

  • Ref: TAF0001-115198

  • *Mandatory photo required - Individual close up photos (Macro setting) of each card to show fibres installed on this project. Try to show Slot & Port number Photo rotated so that label is horizontal on page.

Section 14

Labelling 2M Twisted Pair Cables Subrack end

  • a. Both 2M Twisted Pair cables Eq IN & Eq OUT labelled at the subrack LTU end with SLOT & Port Range 15-20mm from connector around both cables

  • b. 2M cable labels orientated so that they read away from the connector

  • Ref: TAF0001-115198

  • Insert photos please

Section 15

Labelling 2M DDF

  • a. Each Strip contains NE Location

  • b. Each Strip contains NE ID

  • c. Each Strip contains LTU Slot position

  • d. Each Strip contains DDF Block position

  • e. Each Strip contains Port number

  • f. Monitoring ports for relevant LTU’s left blank (PORT 32)

  • Ref: TAF0001-115198

  • *Mandatory photo required - Photos of the front of the blocks clearly showing the label details.

Section 16

Labelling Alarm IDF

  • a. APDP location correct (front of label) F/S/R/Sr

  • b. CB number (rear of label)

  • Ref: TM 00330

  • *Mandatory photo required - Photos or front and rear of the labels.

Section 17

Labelling SFW Couplers

  • a. Label visible without moving coupler

  • b. Label placed in correct position and contains LIS & NE-ID

  • c. All couplers labelled correctly

  • Ref: CSD 26507

  • *Mandatory photo required - Macro close up showing labelling on SFW coupler.

Section 18

Labelling OFDF

  • a. Each Drawer labelled with LiS

  • b. Splice Trays label indicating fibre sheath code & fibre range

  • c. Pigtail labelled with Fibre No

  • d. Patch panel layout card provided & updated to show LiS & relation between Positions on patch panel & Sheath Code/Fibre No.

  • e. Patchcord labelled with Sheath code & Fibre No.

  • Ref: SP000511

  • *Mandatory photo required - Take Photo of either Splice tray or Patch panel depending project

Section 19

Labelling HDODF

  • a. Each Subrack labelled with LiS, Sheath ID, Fibre range & Subrack type

  • b. Trays label indicating fibre sheath code & fibre range

  • c. Pigtail labelled with Fibre No

  • c. Patchcord labelled with Sheath code & Fibre No.

  • Ref: TM00183 A01

  • *Mandatory photo required - Take wide Photo of Patch panel to show tray label fibre numbering & patchcord label

Section 20

Labelling LOD

  • a. LOD panel labelled with LIS, LOD No, Max demand current, where it is fed from, plane & SP & WO

  • b. LOD labelled for correct CB allocation, NE LIS, Feed No & CB rating

  • c. LOD labelled for correct CB allocation

  • Ref: 007 338 E5-6

  • Insert photos please

Section 21

Labelling LOD Power Cables

  • a. Cables labelled at LOD with NE LIS, RF1 or2 & CB position

  • b. Cables labelled at APDP end (RF1 & RF2)

  • Ref: 007 338 E5-6

  • Insert photos please

Section 22

Labelling MRSPP/SRPP Cables

  • a. SRPP label on BOTH Ends of CCB to SPC connecting cable

  • b. SRPP label at 1 Metre interval above/below equipment racks

  • c. SRPP label on either end of the SUITE cable

  • Insert photos please

Section 23

Labelling SPC / CCB bars

  • a. Single Point of Connection Bar marked as “SPC”

  • b. CCB bar labelled CCB and also has an SDH MSRPP /SRPP label

  • Insert photos please

Completion

  • General Comments

  • This is the end of Photo Audit. Your audit result can be found under "Audits" menu. You can edit, preview and send your result via Email

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.