All 80 Amp isolators with affixed apartment identification.
-
All 100 Amp Bemco fuse carriers (AND) fuse holder marked up with apartment number. (Fuses go back into correct carrier)<br>
-
All dead test results received from SWA installation at 1st fix stage from installers.<br>
-
All apartments have been function tested (Proved at 2nd fix stage correct supply upon fuse installation)<br>
-
All apartments re -energised 1 apartment at a time. (To confirm Meter, isolator, apartment are linked)
-
All apartments that are having meters installed have the corresponding completed certificate on Asite (This is to ensure only completed apartments are having meters installed).
-
All hoist apartment either have a completed fuse installed or a blank empty fuse holder installed with security tag /"Lead" seal (Do Not Remove) tag
-
All crane tie apartment either have a completed fuse installed or a blank empty fuse holder installed with security tag /"Lead" seal (Do Not Remove) tag.
-
Only associated Bemco riser keys have been signed out for the planned meter installation works.
-