Title Page
-
Daily Chiller logging Report for month:
-
Doc No. SOP-COR-GEN-13-F09
-
Site:
-
Conducted on
-
Prepared by
-
Location:
-
Personnel
Logging - Chiller 1
Carrier: 19XR 8787
-
Which chiller are running?
- Chiller 1
- Chiller 2
- Chiller 3
- Chiller 4
Chiller 1 LOGGING
GENERAL
-
POWER METER READING (SUM MWH):
-
% CURRENT LOAD (%):
-
MOTOR KW:
-
MOTOR KWH:
COOLER
-
CHILLED WATER IN TEMPERATURE (Design = 14 - 15 °C):
-
CHILLED WATER OUT TEMPERATURE (Design = 4°C):
-
EVAPORATOR PRESSURE (Reference= >28 PSI/193 Kpa):
-
EVAPORATOR APPROACH (Reference= < 0.6 °C):
-
CHW IN PRESSURE (PSI):
-
CHW OUT PRESSURE (PSI):
-
WATER PRESSURE DROP (Design= 8.1 PSI):
CONDENSER
-
CONDENSER WATER IN TEMPERATURE (Design = 30.5 °C):
-
CONDENSER WATER OUT TEMPERATURE (Design = 35.7 °C):
-
CONDENSER PRESSURE (Reference = < 124 PSI/ 855 Kpa):
-
CONDENSER APPROACH (Reference = < 0.6°C):
-
COND. WATER IN PRESSURE (PSI):
-
COND. WATER OUT PRESSURE (PSI):
-
WATER PRESSURE DROP (Design = 8.7 PSI):
COMPRESSOR
-
OIL SUMP TEMPERATURE (Reference = 50 - 60 °C):
-
OIL PUMP DELTA PRESSURE (Reference > 16 PSI/110 Kpa):
-
COMPRESSOR DISCHARGE TEMPERATURE (Discharge Temperature Alert = 85 °C):
-
COMPRESSOR THRUST BEARING TEMPERATURE (Bearing Temperature Alert = 79 °C):
-
COMPRESSOR MOTOR WINDING TEMPERATURE (Motor temperature override = 66 °C):
-
REMARKS:
Logging - Chiller 2
Carrier: 19XR 8787
Chiller 2 LOGGING
GENERAL
-
POWER METER READING (SUM MWH):
-
% CURRENT LOAD (%):
-
MOTOR KW:
-
MOTOR KWH:
COOLER
-
CHILLED WATER IN TEMPERATURE (Design = 14 - 15 °C):
-
CHILLED WATER OUT TEMPERATURE (Design = 4°C):
-
EVAPORATOR PRESSURE (Reference= >28 PSI/193 Kpa):
-
EVAPORATOR APPROACH (Reference= < 0.6 °C):
-
CHW IN PRESSURE (PSI):
-
CHW OUT PRESSURE (PSI):
-
WATER PRESSURE DROP (Design= 8.1 PSI):
CONDENSER
-
CONDENSER WATER IN TEMPERATURE (Design = 30.5 °C):
-
CONDENSER WATER OUT TEMPERATURE (Design = 35.7 °C):
-
CONDENSER PRESSURE (Reference = < 124 PSI/ 855 Kpa):
-
CONDENSER APPROACH (Reference = < 0.6°C):
-
COND. WATER IN PRESSURE (PSI):
-
COND. WATER OUT PRESSURE (PSI):
-
WATER PRESSURE DROP (Design = 8.7 PSI):
COMPRESSOR
-
OIL SUMP TEMPERATURE (Reference = 50 - 60 °C):
-
OIL PUMP DELTA PRESSURE (Reference > 16 PSI/110 Kpa):
-
COMPRESSOR DISCHARGE TEMPERATURE (Discharge Temperature Alert = 85 °C):
-
COMPRESSOR THRUST BEARING TEMPERATURE (Bearing Temperature Alert = 79 °C):
-
COMPRESSOR MOTOR WINDING TEMPERATURE (Motor temperature override = 66 °C):
-
REMARKS:
Logging - Chiller 3
Carrier: 19XR 8787
Chiller 3 LOGGING
GENERAL
-
POWER METER READING (SUM MWH):
-
% CURRENT LOAD (%):
-
MOTOR KW:
-
MOTOR KWH:
COOLER
-
CHILLED WATER IN TEMPERATURE (Design = 14 - 15 °C):
-
CHILLED WATER OUT TEMPERATURE (Design = 4°C):
-
EVAPORATOR PRESSURE (Reference= >28 PSI/193 Kpa):
-
EVAPORATOR APPROACH (Reference= < 0.6 °C):
-
CHW IN PRESSURE (PSI):
-
CHW OUT PRESSURE (PSI):
-
WATER PRESSURE DROP (Design= 8.1 PSI):
CONDENSER
-
CONDENSER WATER IN TEMPERATURE (Design = 30.5 °C):
-
CONDENSER WATER OUT TEMPERATURE (Design = 35.7 °C):
-
CONDENSER PRESSURE (Reference = < 124 PSI/ 855 Kpa):
-
CONDENSER APPROACH (Reference = < 0.6°C):
-
COND. WATER IN PRESSURE (PSI):
-
COND. WATER OUT PRESSURE (PSI):
-
WATER PRESSURE DROP (Design = 8.7 PSI):
COMPRESSOR
-
OIL SUMP TEMPERATURE (Reference = 50 - 60 °C):
-
OIL PUMP DELTA PRESSURE (Reference > 16 PSI/110 Kpa):
-
COMPRESSOR DISCHARGE TEMPERATURE (Discharge Temperature Alert = 85 °C):
-
COMPRESSOR THRUST BEARING TEMPERATURE (Bearing Temperature Alert = 79 °C):
-
COMPRESSOR MOTOR WINDING TEMPERATURE (Motor temperature override = 66 °C):
-
REMARKS:
Logging - Chiller 4
Carrier: 19XR 8787
Chiller 4 LOGGING
GENERAL
-
POWER METER READING (SUM MWH):
-
% CURRENT LOAD (%):
-
MOTOR KW:
-
MOTOR KWH:
COOLER
-
CHILLED WATER IN TEMPERATURE (Design = 14 - 15 °C):
-
CHILLED WATER OUT TEMPERATURE (Design = 4°C):
-
EVAPORATOR PRESSURE (Reference= >28 PSI/193 Kpa):
-
EVAPORATOR APPROACH (Reference= < 0.6 °C):
-
CHW IN PRESSURE (PSI):
-
CHW OUT PRESSURE (PSI):
-
WATER PRESSURE DROP (Design= 8.1 PSI):
CONDENSER
-
CONDENSER WATER IN TEMPERATURE (Design = 30.5 °C):
-
CONDENSER WATER OUT TEMPERATURE (Design = 35.7 °C):
-
CONDENSER PRESSURE (Reference = < 124 PSI/ 855 Kpa):
-
CONDENSER APPROACH (Reference = < 0.6°C):
-
COND. WATER IN PRESSURE (PSI):
-
COND. WATER OUT PRESSURE (PSI):
-
WATER PRESSURE DROP (Design = 8.7 PSI):
COMPRESSOR
-
OIL SUMP TEMPERATURE (Reference = 50 - 60 °C):
-
OIL PUMP DELTA PRESSURE (Reference > 16 PSI/110 Kpa):
-
COMPRESSOR DISCHARGE TEMPERATURE (Discharge Temperature Alert = 85 °C):
-
COMPRESSOR THRUST BEARING TEMPERATURE (Bearing Temperature Alert = 79 °C):
-
COMPRESSOR MOTOR WINDING TEMPERATURE (Motor temperature override = 66 °C):
-
REMARKS
PUMP Condition
PRIMARY CHILLED WATER PUMP CONDITION
-
Which primary chilled water pump are operating?
- PCHWP 1
- PCHWP 2
- PCHWP 3
- PCHWP 4
-
Any Abnormal noise?
-
Any leaking?
SECONDARY CHILLED WATER PUMP CONDITION
-
Which secondary chilled water pump are operating?
- SCHWP-1
- SCHWP-2
- SCHWP-3
- SCHWP-4
- SCHWP-5
- SCHWP-6
- SCHWP-7
- SCHWP-8
- SCHWP-9
- SCHWP-10
- SCHWP-11
- SCHWP-E1-2-1
- SCHWP-E1-2-2
- SCHWP-E1-2-3
-
Any Abnormal noise?
-
Any Leaking?
CONDENSER WATER PUMP CONDITION
-
Which condenser water pump are operating?
- CWP-1
- CWP-2
- CWP-3
- CWP-4
-
Any Abnormal noise?
-
Any Leaking?
-
REMARKS:
Cooling Tower Condition
COOLING TOWER CONDITION
-
Which cooling tower are operating?
- Cooling Tower 1
- Cooling Tower 2
- Cooling Tower 3
- Cooling Tower 4
-
Any Abnormal noise?
-
Any leaking?
-
Water level High (H) or Low (L):
-
Inlet motorised valve open or close:
-
Outlet motorised valve open or close:
-
PHASE 1 Ampere:
-
PHASE 2 Ampere:
-
PHASE 3 Ampere:
-
Running frequency (hz):
-
Energy consumption (KWH):
-
REMARKS:
SIGN OFF
-
Recorded by:
-
Verified by: