Title Page

  • Daily Chiller logging Report for month:

  • Doc No. SOP-COR-GEN-13-F09

  • Site:

  • Conducted on

  • Prepared by

  • Location:
  • Personnel

Logging - Chiller 1

Carrier: 19XR 8787

  • Which chiller are running?

Chiller 1 LOGGING

GENERAL

  • POWER METER READING (SUM MWH):

  • % CURRENT LOAD (%):

  • MOTOR KW:

  • MOTOR KWH:

COOLER

  • CHILLED WATER IN TEMPERATURE (Design = 14 - 15 °C):

  • CHILLED WATER OUT TEMPERATURE (Design = 4°C):

  • EVAPORATOR PRESSURE (Reference= >28 PSI/193 Kpa):

  • EVAPORATOR APPROACH (Reference= < 0.6 °C):

  • CHW IN PRESSURE (PSI):

  • CHW OUT PRESSURE (PSI):

  • WATER PRESSURE DROP (Design= 8.1 PSI):

CONDENSER

  • CONDENSER WATER IN TEMPERATURE (Design = 30.5 °C):

  • CONDENSER WATER OUT TEMPERATURE (Design = 35.7 °C):

  • CONDENSER PRESSURE (Reference = < 124 PSI/ 855 Kpa):

  • CONDENSER APPROACH (Reference = < 0.6°C):

  • COND. WATER IN PRESSURE (PSI):

  • COND. WATER OUT PRESSURE (PSI):

  • WATER PRESSURE DROP (Design = 8.7 PSI):

COMPRESSOR

  • OIL SUMP TEMPERATURE (Reference = 50 - 60 °C):

  • OIL PUMP DELTA PRESSURE (Reference > 16 PSI/110 Kpa):

  • COMPRESSOR DISCHARGE TEMPERATURE (Discharge Temperature Alert = 85 °C):

  • COMPRESSOR THRUST BEARING TEMPERATURE (Bearing Temperature Alert = 79 °C):

  • COMPRESSOR MOTOR WINDING TEMPERATURE (Motor temperature override = 66 °C):

  • REMARKS:

Logging - Chiller 2

Carrier: 19XR 8787

Chiller 2 LOGGING

GENERAL

  • POWER METER READING (SUM MWH):

  • % CURRENT LOAD (%):

  • MOTOR KW:

  • MOTOR KWH:

COOLER

  • CHILLED WATER IN TEMPERATURE (Design = 14 - 15 °C):

  • CHILLED WATER OUT TEMPERATURE (Design = 4°C):

  • EVAPORATOR PRESSURE (Reference= >28 PSI/193 Kpa):

  • EVAPORATOR APPROACH (Reference= < 0.6 °C):

  • CHW IN PRESSURE (PSI):

  • CHW OUT PRESSURE (PSI):

  • WATER PRESSURE DROP (Design= 8.1 PSI):

CONDENSER

  • CONDENSER WATER IN TEMPERATURE (Design = 30.5 °C):

  • CONDENSER WATER OUT TEMPERATURE (Design = 35.7 °C):

  • CONDENSER PRESSURE (Reference = < 124 PSI/ 855 Kpa):

  • CONDENSER APPROACH (Reference = < 0.6°C):

  • COND. WATER IN PRESSURE (PSI):

  • COND. WATER OUT PRESSURE (PSI):

  • WATER PRESSURE DROP (Design = 8.7 PSI):

COMPRESSOR

  • OIL SUMP TEMPERATURE (Reference = 50 - 60 °C):

  • OIL PUMP DELTA PRESSURE (Reference > 16 PSI/110 Kpa):

  • COMPRESSOR DISCHARGE TEMPERATURE (Discharge Temperature Alert = 85 °C):

  • COMPRESSOR THRUST BEARING TEMPERATURE (Bearing Temperature Alert = 79 °C):

  • COMPRESSOR MOTOR WINDING TEMPERATURE (Motor temperature override = 66 °C):

  • REMARKS:

Logging - Chiller 3

Carrier: 19XR 8787

Chiller 3 LOGGING

GENERAL

  • POWER METER READING (SUM MWH):

  • % CURRENT LOAD (%):

  • MOTOR KW:

  • MOTOR KWH:

COOLER

  • CHILLED WATER IN TEMPERATURE (Design = 14 - 15 °C):

  • CHILLED WATER OUT TEMPERATURE (Design = 4°C):

  • EVAPORATOR PRESSURE (Reference= >28 PSI/193 Kpa):

  • EVAPORATOR APPROACH (Reference= < 0.6 °C):

  • CHW IN PRESSURE (PSI):

  • CHW OUT PRESSURE (PSI):

  • WATER PRESSURE DROP (Design= 8.1 PSI):

CONDENSER

  • CONDENSER WATER IN TEMPERATURE (Design = 30.5 °C):

  • CONDENSER WATER OUT TEMPERATURE (Design = 35.7 °C):

  • CONDENSER PRESSURE (Reference = < 124 PSI/ 855 Kpa):

  • CONDENSER APPROACH (Reference = < 0.6°C):

  • COND. WATER IN PRESSURE (PSI):

  • COND. WATER OUT PRESSURE (PSI):

  • WATER PRESSURE DROP (Design = 8.7 PSI):

COMPRESSOR

  • OIL SUMP TEMPERATURE (Reference = 50 - 60 °C):

  • OIL PUMP DELTA PRESSURE (Reference > 16 PSI/110 Kpa):

  • COMPRESSOR DISCHARGE TEMPERATURE (Discharge Temperature Alert = 85 °C):

  • COMPRESSOR THRUST BEARING TEMPERATURE (Bearing Temperature Alert = 79 °C):

  • COMPRESSOR MOTOR WINDING TEMPERATURE (Motor temperature override = 66 °C):

  • REMARKS:

Logging - Chiller 4

Carrier: 19XR 8787

Chiller 4 LOGGING

GENERAL

  • POWER METER READING (SUM MWH):

  • % CURRENT LOAD (%):

  • MOTOR KW:

  • MOTOR KWH:

COOLER

  • CHILLED WATER IN TEMPERATURE (Design = 14 - 15 °C):

  • CHILLED WATER OUT TEMPERATURE (Design = 4°C):

  • EVAPORATOR PRESSURE (Reference= >28 PSI/193 Kpa):

  • EVAPORATOR APPROACH (Reference= < 0.6 °C):

  • CHW IN PRESSURE (PSI):

  • CHW OUT PRESSURE (PSI):

  • WATER PRESSURE DROP (Design= 8.1 PSI):

CONDENSER

  • CONDENSER WATER IN TEMPERATURE (Design = 30.5 °C):

  • CONDENSER WATER OUT TEMPERATURE (Design = 35.7 °C):

  • CONDENSER PRESSURE (Reference = < 124 PSI/ 855 Kpa):

  • CONDENSER APPROACH (Reference = < 0.6°C):

  • COND. WATER IN PRESSURE (PSI):

  • COND. WATER OUT PRESSURE (PSI):

  • WATER PRESSURE DROP (Design = 8.7 PSI):

COMPRESSOR

  • OIL SUMP TEMPERATURE (Reference = 50 - 60 °C):

  • OIL PUMP DELTA PRESSURE (Reference > 16 PSI/110 Kpa):

  • COMPRESSOR DISCHARGE TEMPERATURE (Discharge Temperature Alert = 85 °C):

  • COMPRESSOR THRUST BEARING TEMPERATURE (Bearing Temperature Alert = 79 °C):

  • COMPRESSOR MOTOR WINDING TEMPERATURE (Motor temperature override = 66 °C):

  • REMARKS

PUMP Condition

PRIMARY CHILLED WATER PUMP CONDITION

  • Which primary chilled water pump are operating?

  • Any Abnormal noise?

  • Any leaking?

SECONDARY CHILLED WATER PUMP CONDITION

  • Which secondary chilled water pump are operating?

  • Any Abnormal noise?

  • Any Leaking?

CONDENSER WATER PUMP CONDITION

  • Which condenser water pump are operating?

  • Any Abnormal noise?

  • Any Leaking?

  • REMARKS:

Cooling Tower Condition

COOLING TOWER CONDITION

  • Which cooling tower are operating?

  • Any Abnormal noise?

  • Any leaking?

  • Water level High (H) or Low (L):

  • Inlet motorised valve open or close:

  • Outlet motorised valve open or close:

  • PHASE 1 Ampere:

  • PHASE 2 Ampere:

  • PHASE 3 Ampere:

  • Running frequency (hz):

  • Energy consumption (KWH):

  • REMARKS:

SIGN OFF

  • Recorded by:

  • Verified by:

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.