Information

  • Division

  • Site

  • House Type Range

  • House Type Series

  • House Type

  • House Type Mix

  • Date

  • Prepared by

  • Personnel

1.0 - Externals

  • 1.1 - Are there any landscaping and boundary treatment concerns?

  • 1.2 - Are there any good examples of landscaping and boundary treatment?

2.0 - Elevation Treatment

  • 2.1 - What is the general condition of the elevation finish (brick/render)?

  • 2.2 - Are the windows correct for this house type?

  • 2.2 - How would you rate the appearance of the windows?

  • 2.3 - Are the doors the correct type/colour for this house type?

  • 2.4 - Are the rainwater goods positioned correctly?

  • 2.5 - Are the rainwater goods the correct specification with fixings as specification?

  • Gutter brackets 750mm c/c with 2 fixings. RWP brackets to be 1800mm min

  • 2.6 - Are the utilities in the correct location?

  • 2.7 - If there is an alarm, is it in the correct location?

  • 2.8 - Is the roof tile the correct type for this house type?

  • 2.9 - Are the extract fans installed suitably?

  • 2.10 - Are the tiles fitted to your satisfaction?

  • 2.11 - What are the verges like?

  • Gables not highly prominent should have dry verges and block ends to ridge tiles - wet verges to front elevations should have opens ended, pointed ridge tiles.

  • 2.12 - Are the barge facias and rafter ends all in accordance with the detail?

  • 2.13 - Is there renewable technology in the roof?

  • How does it look?

  • 2.14 - Is the window tile creasing correct?<br>

  • Window tile creasing to extend 50mm beyond jamb with even tile sizes and mortar applied to all joints.

3.0 - Hallway

  • 3.1 - Is the front door ironmongery correct?

  • 3.2 - Are switches and sockets in the correct location?

  • 3.3 - Are the switches and sockets the correct specification?

  • 3.4 - Is the lighting in the correct location?

  • 3.5 - Is the lighting the correct specification?

  • 3.6 - Is the radiator in the correct location?

  • 3.7 - Is the radiator the correct size and specification?

  • 3.8 - Are the trickle vents over frame vents?

  • 3.9 - Are the skirting and architrave sizes correct?

  • Ground floor
    Skirting on all types to be 193mm high
    Architrave <1400sqft to be 55mm >1400sqft to be 69mm
    First floor
    Skirting <1400sqft to be 119mm >1400sqft to be 193mm
    Architrave <1400sqft to be 55mm > 1400sqft to be 93mm

  • 3.10 - Do window boards extend 25mm beyond wall face?

  • 3.11 - Is the staircase the correct configuration as the drawing?

  • 3.12 - Are the handrails and balusters in accordance with specification?

4.0 - Cloaks

  • 4.3 - Is the lighting in the correct location?

  • 4.4 - Is the lighting the correct specification?

  • 4.5 - Is the radiator in the correct location?

  • 4.6 - Is the radiator the correct size and specification?

  • 4.7 - Are the trickle vents over frame vents?

  • 4.8 - Are the skirting and architrave sizes correct?

  • Ground floor
    Skirting on all types to be 193mm high
    Architrave <1400sqft to be 55mm >1400sqft to be 69mm
    First floor
    Skirting <1400sqft to be 119mm >1400sqft to be 193mm
    Architrave <1400sqft to be 55mm > 1400sqft to be 93mm

  • 4.9 - Do window boards extend 25mm beyond wall face?

  • 4.10 - Does corner basin to have chrome water trap?

  • 4.11 - Does flat wall basin have semi pedestal?

  • 4.12 - Does WC have stop valve access point?

5.0 - Lounge

  • 5.1 - Are switches and sockets in the correct location?

  • 5.2 - Are the switches and sockets the correct specification?

  • 5.3 - Is the lighting in the correct location?

  • 5.4 - Is the lighting the correct specification?

  • 5.5 - Is the radiator in the correct location?

  • 5.6 - Is the radiator the correct size and specification?

  • 5.7 - Are the trickle vents over frame vents?

  • 5.8 - Are the skirting and architrave sizes correct?

  • Ground floor
    Skirting on all types to be 193mm high
    Architrave <1400sqft to be 55mm >1400sqft to be 69mm
    First floor
    Skirting <1400sqft to be 119mm >1400sqft to be 193mm
    Architrave <1400sqft to be 55mm > 1400sqft to be 93mm

  • 5.9 - Do window boards extend 25mm beyond wall face?

  • 5.10 - Is there a sound system?

  • Are the sound system speakers located symmetrically?

6.0 - Dining Room

  • 6.1 - Are switches and sockets in the correct location?

  • 6.2 - Are the switches and sockets the correct specification?

  • 6.3 - Is the lighting in the correct location?

  • 6.4 - Is the lighting the correct specification?

  • 6.5 - Is the radiator in the correct location?

  • 6.6 - Is the radiator the correct size and specification?

  • 6.7 - Are the trickle vents over frame vents?

  • 6.8 - Are the skirting and architrave sizes correct?

  • Ground floor
    Skirting on all types to be 193mm high
    Architrave <1400sqft to be 55mm >1400sqft to be 69mm
    First floor
    Skirting <1400sqft to be 119mm >1400sqft to be 193mm
    Architrave <1400sqft to be 55mm > 1400sqft to be 93mm

  • 6.9 - Do window boards extend 25mm beyond wall face?

  • 6.10 - Is there a sound system?

  • Are the sound system speakers located symmetrically?

7.0 - Kitchen

  • 7.1 - Are switches and sockets in the correct location?

  • 7.2 - Are the switches and sockets the correct specification?

  • 7.3 - Is the lighting in the correct location?

  • 7.4 - Is the lighting the correct specification?

  • 7.5 - Is the radiator in the correct location?

  • 7.6 - Is the radiator the correct size and specification?

  • 7.7 - Are the trickle vents over frame vents?

  • 7.8 - Are the skirting and architrave sizes correct?

  • Ground floor
    Skirting on all types to be 193mm high
    Architrave <1400sqft to be 55mm >1400sqft to be 69mm
    First floor
    Skirting <1400sqft to be 119mm >1400sqft to be 193mm
    Architrave <1400sqft to be 55mm > 1400sqft to be 93mm

  • 7.9 - Do window boards extend 25mm beyond wall face?

  • 7.10 - Is there a sound system?

  • Are the sound system speakers located symmetrically?

  • 7.11 - Which kitchen manufacturer is used?

  • Are there any comments or images relevant to the visit?

  • 7.12 - Are the appliances ventilated in the plinth?

8.0 - Landing

  • 8.1 - Are switches and sockets in the correct location?

  • 8.2 - Are the switches and sockets the correct specification?

  • 8.3 - Is the lighting in the correct location?

  • 8.4 - Is the lighting the correct specification?

  • 8.5 - Is the radiator in the correct location?

  • 8.6 - Is the radiator the correct size and specification?

  • 8.7 - Are the trickle vents over frame vents?

  • 8.8 - Are the skirting and architrave sizes correct?

  • Ground floor
    Skirting on all types to be 193mm high
    Architrave <1400sqft to be 55mm >1400sqft to be 69mm
    First floor
    Skirting <1400sqft to be 119mm >1400sqft to be 193mm
    Architrave <1400sqft to be 55mm > 1400sqft to be 93mm

  • 8.9 - Do window boards extend 25mm beyond wall face?

  • 8.10 - Is the staircase the correct configuration as the drawing?

  • 8.11 - Are the handrails and balusters in accordance with specification?

  • 8.12 - is the loft access in the correct location?

9.0 - Bathroom

  • 9.1 - Are the electrics in the correct location?

  • 9.2 - Are the electrics the correct specification?

  • 9.3 - Is the radiator in the correct location?

  • 9.4 - Is the radiator the correct size and specification?

  • 9.5 - Are the trickle vents over frame vents?

  • 9.6 - Are the skirting and architrave sizes correct?

  • Ground floor
    Skirting on all types to be 193mm high
    Architrave <1400sqft to be 55mm >1400sqft to be 69mm
    First floor
    Skirting <1400sqft to be 119mm >1400sqft to be 193mm
    Architrave <1400sqft to be 55mm > 1400sqft to be 93mm

  • 9.7 - Do window boards extend 25mm beyond wall face?

  • 9.8 - Is the sanitary ware in the correct location?

  • 9.9 - Is the sanitary ware the correct specification?

  • 9.10 - Is the tiling laid as the elevations with the correct trim?

10.0 - Ensuite

  • 10.1 - Are the electrics in the correct location?

  • 10.2 - Are the electrics the correct specification?

  • 10.3 - Is the radiator in the correct location?

  • 10.4 - Is the radiator the correct size and specification?

  • 10.5 - Are the trickle vents over frame vents?

  • 10.6 - Are the skirting and architrave sizes correct?

  • Ground floor
    Skirting on all types to be 193mm high
    Architrave <1400sqft to be 55mm >1400sqft to be 69mm
    First floor
    Skirting <1400sqft to be 119mm >1400sqft to be 193mm
    Architrave <1400sqft to be 55mm > 1400sqft to be 93mm

  • 10.7 - Do window boards extend 25mm beyond wall face?

  • 10.8 - Is the sanitary ware in the correct location?

  • 10.9 - Is the sanitary ware the correct specification?

  • 10.10 - Is the tiling laid as the elevations with the correct trim?

11.0 - Bedrooms

  • 11.1 - Are switches and sockets in the correct location?

  • 11.2 - Are the switches and sockets the correct specification?

  • 11.3 - Is the lighting in the correct location?

  • 11.4 - Is the lighting the correct specification?

  • 11.5 - Is the radiator in the correct location?

  • 11.6 - Is the radiator the correct size and specification?

  • 11.7 - Are the trickle vents over frame vents?

  • 11.8 - Are the skirting and architrave sizes correct?

  • Ground floor
    Skirting on all types to be 193mm high
    Architrave <1400sqft to be 55mm >1400sqft to be 69mm
    First floor
    Skirting <1400sqft to be 119mm >1400sqft to be 193mm
    Architrave <1400sqft to be 55mm > 1400sqft to be 93mm

  • 11.9 - Do window boards extend 25mm beyond wall face?

  • 11.10 - Is there a sound system?

  • Are the sound system speakers located symmetrically?

  • 11.11 - Are there fitted wardrobes?

General Notes

  • Are there any comments or images relevant to the visit?

Sign Off

  • On site representative

  • Auditor's signature

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.