System Information

  • Insert System Specs & Testing Advice

Monthly Inspection / Test Schedule

  • Sound Equipment: Inspect to ensure clearly visible and readily accessible. Clean and correctly labelled

  • Warning System Test: Simulate an alarm condition and confirm alert and evacuation tones

  • Controls: Ensure all controls are returned to their normal position

  • Intercom Equipment: Inspect to ensure clearly visible & readily accessible. Clean and correctly labelled

Six Monthly Inspection / Test Schedule

  • Warning System Indication: Simulate an alarm condition via the fire system to automatic mode

  • Reset: Test the operation of the reset function

  • Aural Indicators: Test the operation of the aural indicators

  • Controls: Test the operation of all the required controls

  • Warden Intercom Points (WIP): Inspect to ensure clearly visible & readily accessible. Clean and correctly labelled

  • WIP: Inspect all WIP's to ensure there is no mechanical damage

  • WIP Operation Instructions: Inspect all instructions to ensure they are clearly visible and legible

  • Battery Enclosure Intercom System: Inspect battery enclosure for evidence of corrosion

  • WIP Location: Inspect all evacuation zones to ensure at least one WIP is installed

Yearly Inspection / Test Schedule

  • Call Points: Inspect all call points for any condition that is likely to adversely affect their operation

  • Visual Warning Devices (VWD's): Inspect all devices for any condition or damage that is likely to adversely affect their operation

  • Other Warning Devices: Inspect all devices to ensure that they are in place

  • Block Plan: Inspect block plans and zone drawings to ensure that they are legible and current

  • Battery Enclosure Sound System: Inspect enclosure for evidence of corrosion

  • Fault: Simulate a speaker, emergency call point, visual warning device and WIP fault for every circuit. Confirm indication

  • Fault: Simulate fault between the fire system and warning system and confirm indication at the warning panel

  • Visual Indicators: Test the operation of the LED and alphanumeric indicators

  • Battery: Test battery capacity if it has not been replaced within two years - Record results (Provide System Alarm Current & Final Voltage)

  • Ancillary Controls: Test the operational function and ensure device can be correctly initiated

  • Emergency Call Points: Test the operation of all installed emergency call points

  • Visual Warning Devices: Test the operation of all visual warning devices

  • Unprotected Areas: Test all areas - ensure system installed in accordance with the relevant installed standard

  • Functional Test: Confirm that the sound system tones are audible in all areas of the building

  • Override Test: Confirm that the alarm signal override non - emergency audible signals

  • WIP: Initiate a call from and to each WIP & confirm each WIP is indicating and clearly communicating with intercom panel

  • Warden Present Indication: Test the operation of the warden present indication

  • Interface and Control Test: Conduct a functional test with other interfaced systems. Verify with building interface schematic (Sprinkler System, Fire Detection System, other)

  • Battery: Replace if older than two years unless its satisfactorily passes a battery capacity test

Yearly Sound Pressure Level Test

  • Sound Pressure Test: Undertake tests to ensure sound pressure levels in all areas of the building meet the requirements of the Standard to which the system was installed

  • Provide: Area/Zone, Ambient Level dB & Max Level dB

  • Provide: Area/Zone, Ambient Level dB & Max Level dB

  • Provide: Area/Zone, Ambient Level dB & Max Level dB

  • Provide: Area/Zone, Ambient Level dB & Max Level dB

  • Provide: Area/Zone, Ambient Level dB & Max Level dB

  • Provide: Area/Zone, Ambient Level dB & Max Level dB

  • Provide: Area/Zone, Ambient Level dB & Max Level dB

  • Provide: Area/Zone, Ambient Level dB & Max Level dB

  • Provide: Area/Zone, Ambient Level dB & Max Level dB

  • Provide: Area/Zone, Ambient Level dB & Max Level dB

Five Yearly Intelligibility Test

  • Intelligibility Test: Undertake tests to ensure speech intelligibility in all areas of the building meet the requirements of the Standard to which the system was installed

  • Provide: Area/Zone, Min CIS & Max CIS

  • Provide: Area/Zone, Min CIS & Max CIS

  • Provide: Area/Zone, Min CIS & Max CIS

  • Provide: Area/Zone, Min CIS & Max CIS

  • Provide: Area/Zone, Min CIS & Max CIS

  • Provide: Area/Zone, Min CIS & Max CIS

  • Provide: Area/Zone, Min CIS & Max CIS

  • Provide: Area/Zone, Min CIS & Max CIS

  • Provide: Area/Zone, Min CIS & Max CIS

  • Provide: Area/Zone, Min CIS & Max CIS

Sign Off

  • Site Contact Name & Signature:

  • Technician Name & Signature

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.