Title Page
-
Report Number
-
Project Name
-
Date of Inspection
-
Project Number
-
Location
-
P.O. Number
-
Prepared by
-
Inspector’s Signature
Inspection Items
Inspection Item 1
-
Inspection Type
- Column Anchor Rods
- Bolted Connections
- Welded Connections
- Deck Fasteners
- Post-Installed Anchors
- Miscellaneous
-
Type of Bolt(s)
- High-Strength Bolts (Beam/Column Connections)
- Other (Please Specify)
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines
-
Comments/Description
-
Picture(s)
-
Do the bolt assemblies comply with RCSC requirements?
-
Description of deficiency(ies)
- Incorrect Grade - Bolt
- Incorrect Grade - Nut
- Incorrect Grade - Washer
-
Specify grade of bolts installed.
- Grade 5
- Grade 8
- ASTM A307
- Other
-
Please specify
-
Specify grade of installed nuts
-
Specify grade of installed washers.
-
Location(s)/Grid Lines of deficiency(ies)
-
Do the bolt assemblies comply with project requirements?
-
Description of deficiency(ies)
- Field-enlarged holes
- Incorrect bolt grade
- Not properly tightened
- Missing bolts assemblies
- Missing washers
- Missing nuts
- Incorrect bolt size
- Incorrect bolt length
- Incorrect washer grade
- Incorrect washer size
- Incorrect nut grade
- Incorrect nut size
- Other (please specify)
-
Please specify
-
Location(s)/Grid Lines of deficiency(ies)
-
Required bolt tensioning method.
- Snug-Tight Conditions
- Pretensioned
-
Method of pretensioning used
- Tension Control Bolts
- Turn-of-Nut
- Calibrated Torque Wrench
- Direct Tension Indicators (DTI)
-
Have the twist-off splines been correctly severed?
-
Have the bolt assemblies been properly match-marked and turned per RCSC Table 8.2?
-
Have the bolt assemblies been properly tensioned per RCSC Table 8.1?
-
Is the appropriate feeler gage refused entry in at least half of the spaces between the protrusions?
-
Are the DTI protrusions facing away from the connecting plies?
-
(Snug-Tight) Have the plies of the connected elements been brought into firm contact as described in RCSC?
-
(Snug-Tight) Have the bolt assemblies been tightened sufficiently to prevent the turning of the nuts without use of a wrench?
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines
-
Specify Bolt Inspection Type
-
Comments/Description
-
Picture(s)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Location(s)/Grid Lines of deficiency(ies).
-
Location(s)/Grid Lines of deficiency(ies).
-
Weld Category
- Beam Connections
- Joist Connections
- Column Baseplates
- Vertical Bracing
- Miscellaneous Connections
- Moment Connections (Visual)
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Type of fasteners used at supporting steel.
- Arc Spot Welds ("Puddle Welds")
- Mechanical Fasteners
-
Does the visual quality and placement of the arc spot welds comply with the contract drawings and AWS D1.3 (2018), Section 8.1.1?
-
Describe the arc spot weld deficiency(ies).
- Incorrect weld spacing
- Undersized welds
- Incomplete fusion to decking
- Insufficient weld reinforcement (Underfill)
- Other (Please Specify)
-
Required Weld Pattern/Spacing
- 36/3
- 36/4
- 36/5
- 36/7
- 36/10
- 36/14
- 24/4
- 6" On Center
- 8" On Center
- 9" On Center
- 10" On Center
- 12" On Center
- 18" On Center
- 24" On Center
- Other (Please Specify)
-
Please specify the required weld pattern/spacing.
-
Installed Weld Pattern/Spacing
- 36/3
- 36/4
- 36/5
- 36/7
- 36/10
- 36/14
- 24/4
- 6" On Center
- 8" On Center
- 9" On Center
- 10" On Center
- 12" On Center
- 18" On Center
- 24" On Center
- Other (Please Specify)
-
Please specify the installed weld pattern/spacing.
-
Type of Mechanical Fasteners
-
Hilti Fastener Type
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing
- Insufficient penetration
- Excessive penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid lines of deficiency(ies).
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing
- Insufficient penetration
- Excessive penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid lines of deficiency(ies).
-
Describe the type of Hilti fastener.
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing
- Insufficient penetration
- Excessive penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid lines of deficiency(ies).
-
Type of Simpson Strong-Tie Fastener.
- Strong-Drive Self-Drilling X Metal Screw
- Strong-Drive XM Medium Head Metal Screw
- Other
-
Describe the type of Simpson Strong-Tie Fastener.
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Specify type of mechanical fastener.
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Description of the connection type(s)
-
Does the installation of the connection(s) comply with the contract drawings, manufacturer's recommendations, applicable code section?
-
Description of the deficiency.
-
Location(s)/Grid Lines of the deficiency(ies).
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Do the installed conditions comply with the contract drawings, AWS D1.1, AISC, and ACI requirements?
-
Please specify the type of deficiency(ies).
- Loose connection(s)
- Field enlarged baseplate bolt holes (torch-cut)
- Insufficient nut engagement with anchor rod (short anchor)
- Washers not installed
- Nuts not installed
- Incorrect washer grade
- Incorrect nut grade
- Other
- Missing welds at washers
-
Please specify type of deficiency(ies).
-
Location(s)/Grid Lines of deficiency(ies).
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Any other Item(s)/Area(s) inspected?
Inspection Item 2
-
Inspection Type
- Column Anchor Rods
- Bolted Connections
- Welded Connections
- Deck Fasteners
- Post-Installed Anchors
- Miscellaneous
-
Type of Bolt(s)
- High-Strength Bolts (Beam/Column Connections)
- Other (Please Specify)
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines
-
Comments/Description
-
Picture(s)
-
Do the bolt assemblies comply with RCSC requirements?
-
Description of deficiency(ies)
- Incorrect Grade - Bolt
- Incorrect Grade - Nut
- Incorrect Grade - Washer
-
Specify grade of bolts installed.
- Grade 5
- Grade 8
- ASTM A307
- Other
-
Please specify
-
Specify grade of installed nuts
-
Specify grade of installed washers.
-
Location(s)/Grid Lines of deficiency(ies)
-
Do the bolt assemblies comply with project requirements?
-
Description of deficiency(ies)
- Field-enlarged holes
- Incorrect bolt grade
- Not properly tightened
- Missing bolts assemblies
- Missing washers
- Missing nuts
- Incorrect bolt size
- Incorrect bolt length
- Incorrect washer grade
- Incorrect washer size
- Incorrect nut grade
- Incorrect nut size
- Other (please specify)
-
Please specify
-
Location(s)/Grid Lines of deficiency(ies)
-
Required bolt tensioning method.
- Snug-Tight Conditions
- Pretensioned
-
Method of pretensioning used
- Tension Control Bolts
- Turn-of-Nut
- Calibrated Torque Wrench
- Direct Tension Indicators (DTI)
-
Have the twist-off splines been correctly severed?
-
Have the bolt assemblies been properly match-marked and turned per RCSC Table 8.2?
-
Have the bolt assemblies been properly tensioned per RCSC Table 8.1?
-
Is the appropriate feeler gage refused entry in at least half of the spaces between the protrusions?
-
Are the DTI protrusions facing away from the connecting plies?
-
(Snug-Tight) Have the plies of the connected elements been brought into firm contact as described in RCSC?
-
(Snug-Tight) Have the bolt assemblies been tightened sufficiently to prevent the turning of the nuts without use of a wrench?
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines
-
Specify Bolt Inspection Type
-
Comments/Description
-
Picture(s)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Location(s)/Grid Lines of deficiency(ies).
-
Location(s)/Grid Lines of deficiency(ies).
-
Weld Category
- Beam Connections
- Joist Connections
- Column Baseplates
- Vertical Bracing
- Miscellaneous Connections
- Moment Connections (Visual)
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Type of fasteners used at supporting steel.
- Arc Spot Welds ("Puddle Welds")
- Mechanical Fasteners
-
Does the visual quality and placement of the arc spot welds comply with the contract drawings and AWS D1.3 (2018), Section 8.1.1?
-
Describe the arc spot weld deficiency(ies).
- Incorrect weld spacing
- Undersized welds
- Incomplete fusion to decking
- Insufficient weld reinforcement (Underfill)
- Other (Please Specify)
-
Required Weld Pattern/Spacing
- 36/3
- 36/4
- 36/5
- 36/7
- 36/10
- 36/14
- 24/4
- 6" On Center
- 8" On Center
- 9" On Center
- 10" On Center
- 12" On Center
- 18" On Center
- 24" On Center
- Other (Please Specify)
-
Please specify the required weld pattern/spacing.
-
Installed Weld Pattern/Spacing
- 36/3
- 36/4
- 36/5
- 36/7
- 36/10
- 36/14
- 24/4
- 6" On Center
- 8" On Center
- 9" On Center
- 10" On Center
- 12" On Center
- 18" On Center
- 24" On Center
- Other (Please Specify)
-
Please specify the installed weld pattern/spacing.
-
Type of Mechanical Fasteners
-
Hilti Fastener Type
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing
- Insufficient penetration
- Excessive penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid lines of deficiency(ies).
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing
- Insufficient penetration
- Excessive penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid lines of deficiency(ies).
-
Describe the type of Hilti fastener.
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing
- Insufficient penetration
- Excessive penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid lines of deficiency(ies).
-
Type of Simpson Strong-Tie Fastener.
- Strong-Drive Self-Drilling X Metal Screw
- Strong-Drive XM Medium Head Metal Screw
- Other
-
Describe the type of Simpson Strong-Tie Fastener.
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Specify type of mechanical fastener.
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Description of the connection type(s)
-
Does the installation of the connection(s) comply with the contract drawings, manufacturer's recommendations, applicable code section?
-
Description of the deficiency.
-
Location(s)/Grid Lines of the deficiency(ies).
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Do the installed conditions comply with the contract drawings, AWS D1.1, AISC, and ACI requirements?
-
Please specify the type of deficiency(ies).
- Loose connection(s)
- Field enlarged baseplate bolt holes (torch-cut)
- Insufficient nut engagement with anchor rod (short anchor)
- Washers not installed
- Nuts not installed
- Incorrect washer grade
- Incorrect nut grade
- Other
- Missing welds at washers
-
Please specify type of deficiency(ies).
-
Location(s)/Grid Lines of deficiency(ies).
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Any other Item(s)/Area(s) inspected?
Inspection Item 3
-
Inspection Type
- Column Anchor Rods
- Bolted Connections
- Welded Connections
- Deck Fasteners
- Post-Installed Anchors
- Miscellaneous
-
Type of Bolt(s)
- High-Strength Bolts (Beam/Column Connections)
- Other (Please Specify)
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines
-
Comments/Description
-
Picture(s)
-
Do the bolt assemblies comply with RCSC requirements?
-
Description of deficiency(ies)
- Incorrect Grade - Bolt
- Incorrect Grade - Nut
- Incorrect Grade - Washer
-
Specify grade of bolts installed.
- Grade 5
- Grade 8
- ASTM A307
- Other
-
Please specify
-
Specify grade of installed nuts
-
Specify grade of installed washers.
-
Location(s)/Grid Lines of deficiency(ies)
-
Do the bolt assemblies comply with project requirements?
-
Description of deficiency(ies)
- Field-enlarged holes
- Incorrect bolt grade
- Not properly tightened
- Missing bolts assemblies
- Missing washers
- Missing nuts
- Incorrect bolt size
- Incorrect bolt length
- Incorrect washer grade
- Incorrect washer size
- Incorrect nut grade
- Incorrect nut size
- Other (please specify)
-
Please specify
-
Location(s)/Grid Lines of deficiency(ies)
-
Required bolt tensioning method.
- Snug-Tight Conditions
- Pretensioned
-
Method of pretensioning used
- Tension Control Bolts
- Turn-of-Nut
- Calibrated Torque Wrench
- Direct Tension Indicators (DTI)
-
Have the twist-off splines been correctly severed?
-
Have the bolt assemblies been properly match-marked and turned per RCSC Table 8.2?
-
Have the bolt assemblies been properly tensioned per RCSC Table 8.1?
-
Is the appropriate feeler gage refused entry in at least half of the spaces between the protrusions?
-
Are the DTI protrusions facing away from the connecting plies?
-
(Snug-Tight) Have the plies of the connected elements been brought into firm contact as described in RCSC?
-
(Snug-Tight) Have the bolt assemblies been tightened sufficiently to prevent the turning of the nuts without use of a wrench?
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines
-
Specify Bolt Inspection Type
-
Comments/Description
-
Picture(s)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Location(s)/Grid Lines of deficiency(ies).
-
Location(s)/Grid Lines of deficiency(ies).
-
Weld Category
- Beam Connections
- Joist Connections
- Column Baseplates
- Vertical Bracing
- Miscellaneous Connections
- Moment Connections (Visual)
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Type of fasteners used at supporting steel.
- Arc Spot Welds ("Puddle Welds")
- Mechanical Fasteners
-
Does the visual quality and placement of the arc spot welds comply with the contract drawings and AWS D1.3 (2018), Section 8.1.1?
-
Describe the arc spot weld deficiency(ies).
- Incorrect weld spacing
- Undersized welds
- Incomplete fusion to decking
- Insufficient weld reinforcement (Underfill)
- Other (Please Specify)
-
Required Weld Pattern/Spacing
- 36/3
- 36/4
- 36/5
- 36/7
- 36/10
- 36/14
- 24/4
- 6" On Center
- 8" On Center
- 9" On Center
- 10" On Center
- 12" On Center
- 18" On Center
- 24" On Center
- Other (Please Specify)
-
Please specify the required weld pattern/spacing.
-
Installed Weld Pattern/Spacing
- 36/3
- 36/4
- 36/5
- 36/7
- 36/10
- 36/14
- 24/4
- 6" On Center
- 8" On Center
- 9" On Center
- 10" On Center
- 12" On Center
- 18" On Center
- 24" On Center
- Other (Please Specify)
-
Please specify the installed weld pattern/spacing.
-
Type of Mechanical Fasteners
-
Hilti Fastener Type
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing
- Insufficient penetration
- Excessive penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid lines of deficiency(ies).
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing
- Insufficient penetration
- Excessive penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid lines of deficiency(ies).
-
Describe the type of Hilti fastener.
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing
- Insufficient penetration
- Excessive penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid lines of deficiency(ies).
-
Type of Simpson Strong-Tie Fastener.
- Strong-Drive Self-Drilling X Metal Screw
- Strong-Drive XM Medium Head Metal Screw
- Other
-
Describe the type of Simpson Strong-Tie Fastener.
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Specify type of mechanical fastener.
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Description of the connection type(s)
-
Does the installation of the connection(s) comply with the contract drawings, manufacturer's recommendations, applicable code section?
-
Description of the deficiency.
-
Location(s)/Grid Lines of the deficiency(ies).
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Do the installed conditions comply with the contract drawings, AWS D1.1, AISC, and ACI requirements?
-
Please specify the type of deficiency(ies).
- Loose connection(s)
- Field enlarged baseplate bolt holes (torch-cut)
- Insufficient nut engagement with anchor rod (short anchor)
- Washers not installed
- Nuts not installed
- Incorrect washer grade
- Incorrect nut grade
- Other
- Missing welds at washers
-
Please specify type of deficiency(ies).
-
Location(s)/Grid Lines of deficiency(ies).
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Any other Item(s)/Area(s) inspected?
Inspection Item 4
-
Inspection Type
- Column Anchor Rods
- Bolted Connections
- Welded Connections
- Deck Fasteners
- Post-Installed Anchors
- Miscellaneous
-
Type of Bolt(s)
- High-Strength Bolts (Beam/Column Connections)
- Other (Please Specify)
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines
-
Comments/Description
-
Picture(s)
-
Do the bolt assemblies comply with RCSC requirements?
-
Description of deficiency(ies)
- Incorrect Grade - Bolt
- Incorrect Grade - Nut
- Incorrect Grade - Washer
-
Specify grade of bolts installed.
- Grade 5
- Grade 8
- ASTM A307
- Other
-
Please specify
-
Specify grade of installed nuts
-
Specify grade of installed washers.
-
Location(s)/Grid Lines of deficiency(ies)
-
Do the bolt assemblies comply with project requirements?
-
Description of deficiency(ies)
- Field-enlarged holes
- Incorrect bolt grade
- Not properly tightened
- Missing bolts assemblies
- Missing washers
- Missing nuts
- Incorrect bolt size
- Incorrect bolt length
- Incorrect washer grade
- Incorrect washer size
- Incorrect nut grade
- Incorrect nut size
- Other (please specify)
-
Please specify
-
Location(s)/Grid Lines of deficiency(ies)
-
Required bolt tensioning method.
- Snug-Tight Conditions
- Pretensioned
-
Method of pretensioning used
- Tension Control Bolts
- Turn-of-Nut
- Calibrated Torque Wrench
- Direct Tension Indicators (DTI)
-
Have the twist-off splines been correctly severed?
-
Have the bolt assemblies been properly match-marked and turned per RCSC Table 8.2?
-
Have the bolt assemblies been properly tensioned per RCSC Table 8.1?
-
Is the appropriate feeler gage refused entry in at least half of the spaces between the protrusions?
-
Are the DTI protrusions facing away from the connecting plies?
-
(Snug-Tight) Have the plies of the connected elements been brought into firm contact as described in RCSC?
-
(Snug-Tight) Have the bolt assemblies been tightened sufficiently to prevent the turning of the nuts without use of a wrench?
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines
-
Specify Bolt Inspection Type
-
Comments/Description
-
Picture(s)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Location(s)/Grid Lines of deficiency(ies).
-
Location(s)/Grid Lines of deficiency(ies).
-
Weld Category
- Beam Connections
- Joist Connections
- Column Baseplates
- Vertical Bracing
- Miscellaneous Connections
- Moment Connections (Visual)
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Type of fasteners used at supporting steel.
- Arc Spot Welds ("Puddle Welds")
- Mechanical Fasteners
-
Does the visual quality and placement of the arc spot welds comply with the contract drawings and AWS D1.3 (2018), Section 8.1.1?
-
Describe the arc spot weld deficiency(ies).
- Incorrect weld spacing
- Undersized welds
- Incomplete fusion to decking
- Insufficient weld reinforcement (Underfill)
- Other (Please Specify)
-
Required Weld Pattern/Spacing
- 36/3
- 36/4
- 36/5
- 36/7
- 36/10
- 36/14
- 24/4
- 6" On Center
- 8" On Center
- 9" On Center
- 10" On Center
- 12" On Center
- 18" On Center
- 24" On Center
- Other (Please Specify)
-
Please specify the required weld pattern/spacing.
-
Installed Weld Pattern/Spacing
- 36/3
- 36/4
- 36/5
- 36/7
- 36/10
- 36/14
- 24/4
- 6" On Center
- 8" On Center
- 9" On Center
- 10" On Center
- 12" On Center
- 18" On Center
- 24" On Center
- Other (Please Specify)
-
Please specify the installed weld pattern/spacing.
-
Type of Mechanical Fasteners
-
Hilti Fastener Type
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing
- Insufficient penetration
- Excessive penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid lines of deficiency(ies).
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing
- Insufficient penetration
- Excessive penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid lines of deficiency(ies).
-
Describe the type of Hilti fastener.
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing
- Insufficient penetration
- Excessive penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid lines of deficiency(ies).
-
Type of Simpson Strong-Tie Fastener.
- Strong-Drive Self-Drilling X Metal Screw
- Strong-Drive XM Medium Head Metal Screw
- Other
-
Describe the type of Simpson Strong-Tie Fastener.
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Specify type of mechanical fastener.
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Description of the connection type(s)
-
Does the installation of the connection(s) comply with the contract drawings, manufacturer's recommendations, applicable code section?
-
Description of the deficiency.
-
Location(s)/Grid Lines of the deficiency(ies).
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Do the installed conditions comply with the contract drawings, AWS D1.1, AISC, and ACI requirements?
-
Please specify the type of deficiency(ies).
- Loose connection(s)
- Field enlarged baseplate bolt holes (torch-cut)
- Insufficient nut engagement with anchor rod (short anchor)
- Washers not installed
- Nuts not installed
- Incorrect washer grade
- Incorrect nut grade
- Other
- Missing welds at washers
-
Please specify type of deficiency(ies).
-
Location(s)/Grid Lines of deficiency(ies).
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Any other Item(s)/Area(s) inspected?
Inspection Item 5
-
Inspection Type
- Column Anchor Rods
- Bolted Connections
- Welded Connections
- Deck Fasteners
- Post-Installed Anchors
- Miscellaneous
-
Type of Bolt(s)
- High-Strength Bolts (Beam/Column Connections)
- Other (Please Specify)
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines
-
Comments/Description
-
Picture(s)
-
Do the bolt assemblies comply with RCSC requirements?
-
Description of deficiency(ies)
- Incorrect Grade - Bolt
- Incorrect Grade - Nut
- Incorrect Grade - Washer
-
Specify grade of bolts installed.
- Grade 5
- Grade 8
- ASTM A307
- Other
-
Please specify
-
Specify grade of installed nuts
-
Specify grade of installed washers.
-
Location(s)/Grid Lines of deficiency(ies)
-
Do the bolt assemblies comply with project requirements?
-
Description of deficiency(ies)
- Field-enlarged holes
- Incorrect bolt grade
- Not properly tightened
- Missing bolts assemblies
- Missing washers
- Missing nuts
- Incorrect bolt size
- Incorrect bolt length
- Incorrect washer grade
- Incorrect washer size
- Incorrect nut grade
- Incorrect nut size
- Other (please specify)
-
Please specify
-
Location(s)/Grid Lines of deficiency(ies)
-
Required bolt tensioning method.
- Snug-Tight Conditions
- Pretensioned
-
Method of pretensioning used
- Tension Control Bolts
- Turn-of-Nut
- Calibrated Torque Wrench
- Direct Tension Indicators (DTI)
-
Have the twist-off splines been correctly severed?
-
Have the bolt assemblies been properly match-marked and turned per RCSC Table 8.2?
-
Have the bolt assemblies been properly tensioned per RCSC Table 8.1?
-
Is the appropriate feeler gage refused entry in at least half of the spaces between the protrusions?
-
Are the DTI protrusions facing away from the connecting plies?
-
(Snug-Tight) Have the plies of the connected elements been brought into firm contact as described in RCSC?
-
(Snug-Tight) Have the bolt assemblies been tightened sufficiently to prevent the turning of the nuts without use of a wrench?
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines
-
Specify Bolt Inspection Type
-
Comments/Description
-
Picture(s)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Location(s)/Grid Lines of deficiency(ies).
-
Location(s)/Grid Lines of deficiency(ies).
-
Weld Category
- Beam Connections
- Joist Connections
- Column Baseplates
- Vertical Bracing
- Miscellaneous Connections
- Moment Connections (Visual)
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Type of fasteners used at supporting steel.
- Arc Spot Welds ("Puddle Welds")
- Mechanical Fasteners
-
Does the visual quality and placement of the arc spot welds comply with the contract drawings and AWS D1.3 (2018), Section 8.1.1?
-
Describe the arc spot weld deficiency(ies).
- Incorrect weld spacing
- Undersized welds
- Incomplete fusion to decking
- Insufficient weld reinforcement (Underfill)
- Other (Please Specify)
-
Required Weld Pattern/Spacing
- 36/3
- 36/4
- 36/5
- 36/7
- 36/10
- 36/14
- 24/4
- 6" On Center
- 8" On Center
- 9" On Center
- 10" On Center
- 12" On Center
- 18" On Center
- 24" On Center
- Other (Please Specify)
-
Please specify the required weld pattern/spacing.
-
Installed Weld Pattern/Spacing
- 36/3
- 36/4
- 36/5
- 36/7
- 36/10
- 36/14
- 24/4
- 6" On Center
- 8" On Center
- 9" On Center
- 10" On Center
- 12" On Center
- 18" On Center
- 24" On Center
- Other (Please Specify)
-
Please specify the installed weld pattern/spacing.
-
Type of Mechanical Fasteners
-
Hilti Fastener Type
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing
- Insufficient penetration
- Excessive penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid lines of deficiency(ies).
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing
- Insufficient penetration
- Excessive penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid lines of deficiency(ies).
-
Describe the type of Hilti fastener.
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing
- Insufficient penetration
- Excessive penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid lines of deficiency(ies).
-
Type of Simpson Strong-Tie Fastener.
- Strong-Drive Self-Drilling X Metal Screw
- Strong-Drive XM Medium Head Metal Screw
- Other
-
Describe the type of Simpson Strong-Tie Fastener.
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Specify type of mechanical fastener.
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Description of the connection type(s)
-
Does the installation of the connection(s) comply with the contract drawings, manufacturer's recommendations, applicable code section?
-
Description of the deficiency.
-
Location(s)/Grid Lines of the deficiency(ies).
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Do the installed conditions comply with the contract drawings, AWS D1.1, AISC, and ACI requirements?
-
Please specify the type of deficiency(ies).
- Loose connection(s)
- Field enlarged baseplate bolt holes (torch-cut)
- Insufficient nut engagement with anchor rod (short anchor)
- Washers not installed
- Nuts not installed
- Incorrect washer grade
- Incorrect nut grade
- Other
- Missing welds at washers
-
Please specify type of deficiency(ies).
-
Location(s)/Grid Lines of deficiency(ies).
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Any other Item(s)/Area(s) inspected?
Inspection Item 6
-
Inspection Type
- Column Anchor Rods
- Bolted Connections
- Welded Connections
- Deck Fasteners
- Post-Installed Anchors
- Miscellaneous
-
Type of Bolt(s)
- High-Strength Bolts (Beam/Column Connections)
- Other (Please Specify)
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines
-
Comments/Description
-
Picture(s)
-
Do the bolt assemblies comply with RCSC requirements?
-
Description of deficiency(ies)
- Incorrect Grade - Bolt
- Incorrect Grade - Nut
- Incorrect Grade - Washer
-
Specify grade of bolts installed.
- Grade 5
- Grade 8
- ASTM A307
- Other
-
Please specify
-
Specify grade of installed nuts
-
Specify grade of installed washers.
-
Location(s)/Grid Lines of deficiency(ies)
-
Do the bolt assemblies comply with project requirements?
-
Description of deficiency(ies)
- Field-enlarged holes
- Incorrect bolt grade
- Not properly tightened
- Missing bolts assemblies
- Missing washers
- Missing nuts
- Incorrect bolt size
- Incorrect bolt length
- Incorrect washer grade
- Incorrect washer size
- Incorrect nut grade
- Incorrect nut size
- Other (please specify)
-
Please specify
-
Location(s)/Grid Lines of deficiency(ies)
-
Required bolt tensioning method.
- Snug-Tight Conditions
- Pretensioned
-
Method of pretensioning used
- Tension Control Bolts
- Turn-of-Nut
- Calibrated Torque Wrench
- Direct Tension Indicators (DTI)
-
Have the twist-off splines been correctly severed?
-
Have the bolt assemblies been properly match-marked and turned per RCSC Table 8.2?
-
Have the bolt assemblies been properly tensioned per RCSC Table 8.1?
-
Is the appropriate feeler gage refused entry in at least half of the spaces between the protrusions?
-
Are the DTI protrusions facing away from the connecting plies?
-
(Snug-Tight) Have the plies of the connected elements been brought into firm contact as described in RCSC?
-
(Snug-Tight) Have the bolt assemblies been tightened sufficiently to prevent the turning of the nuts without use of a wrench?
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines
-
Specify Bolt Inspection Type
-
Comments/Description
-
Picture(s)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Location(s)/Grid Lines of deficiency(ies).
-
Location(s)/Grid Lines of deficiency(ies).
-
Weld Category
- Beam Connections
- Joist Connections
- Column Baseplates
- Vertical Bracing
- Miscellaneous Connections
- Moment Connections (Visual)
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Type of fasteners used at supporting steel.
- Arc Spot Welds ("Puddle Welds")
- Mechanical Fasteners
-
Does the visual quality and placement of the arc spot welds comply with the contract drawings and AWS D1.3 (2018), Section 8.1.1?
-
Describe the arc spot weld deficiency(ies).
- Incorrect weld spacing
- Undersized welds
- Incomplete fusion to decking
- Insufficient weld reinforcement (Underfill)
- Other (Please Specify)
-
Required Weld Pattern/Spacing
- 36/3
- 36/4
- 36/5
- 36/7
- 36/10
- 36/14
- 24/4
- 6" On Center
- 8" On Center
- 9" On Center
- 10" On Center
- 12" On Center
- 18" On Center
- 24" On Center
- Other (Please Specify)
-
Please specify the required weld pattern/spacing.
-
Installed Weld Pattern/Spacing
- 36/3
- 36/4
- 36/5
- 36/7
- 36/10
- 36/14
- 24/4
- 6" On Center
- 8" On Center
- 9" On Center
- 10" On Center
- 12" On Center
- 18" On Center
- 24" On Center
- Other (Please Specify)
-
Please specify the installed weld pattern/spacing.
-
Type of Mechanical Fasteners
-
Hilti Fastener Type
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing
- Insufficient penetration
- Excessive penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid lines of deficiency(ies).
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing
- Insufficient penetration
- Excessive penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid lines of deficiency(ies).
-
Describe the type of Hilti fastener.
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing
- Insufficient penetration
- Excessive penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid lines of deficiency(ies).
-
Type of Simpson Strong-Tie Fastener.
- Strong-Drive Self-Drilling X Metal Screw
- Strong-Drive XM Medium Head Metal Screw
- Other
-
Describe the type of Simpson Strong-Tie Fastener.
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Specify type of mechanical fastener.
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Description of the connection type(s)
-
Does the installation of the connection(s) comply with the contract drawings, manufacturer's recommendations, applicable code section?
-
Description of the deficiency.
-
Location(s)/Grid Lines of the deficiency(ies).
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Do the installed conditions comply with the contract drawings, AWS D1.1, AISC, and ACI requirements?
-
Please specify the type of deficiency(ies).
- Loose connection(s)
- Field enlarged baseplate bolt holes (torch-cut)
- Insufficient nut engagement with anchor rod (short anchor)
- Washers not installed
- Nuts not installed
- Incorrect washer grade
- Incorrect nut grade
- Other
- Missing welds at washers
-
Please specify type of deficiency(ies).
-
Location(s)/Grid Lines of deficiency(ies).
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Any other Item(s)/Area(s) inspected?
Inspection Item 7
-
Inspection Type
- Column Anchor Rods
- Bolted Connections
- Welded Connections
- Deck Fasteners
- Post-Installed Anchors
- Miscellaneous
-
Type of Bolt(s)
- High-Strength Bolts (Beam/Column Connections)
- Other (Please Specify)
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines
-
Comments/Description
-
Picture(s)
-
Do the bolt assemblies comply with RCSC requirements?
-
Description of deficiency(ies)
- Incorrect Grade - Bolt
- Incorrect Grade - Nut
- Incorrect Grade - Washer
-
Specify grade of bolts installed.
- Grade 5
- Grade 8
- ASTM A307
- Other
-
Please specify
-
Specify grade of installed nuts
-
Specify grade of installed washers.
-
Location(s)/Grid Lines of deficiency(ies)
-
Do the bolt assemblies comply with project requirements?
-
Description of deficiency(ies)
- Field-enlarged holes
- Incorrect bolt grade
- Not properly tightened
- Missing bolts assemblies
- Missing washers
- Missing nuts
- Incorrect bolt size
- Incorrect bolt length
- Incorrect washer grade
- Incorrect washer size
- Incorrect nut grade
- Incorrect nut size
- Other (please specify)
-
Please specify
-
Location(s)/Grid Lines of deficiency(ies)
-
Required bolt tensioning method.
- Snug-Tight Conditions
- Pretensioned
-
Method of pretensioning used
- Tension Control Bolts
- Turn-of-Nut
- Calibrated Torque Wrench
- Direct Tension Indicators (DTI)
-
Have the twist-off splines been correctly severed?
-
Have the bolt assemblies been properly match-marked and turned per RCSC Table 8.2?
-
Have the bolt assemblies been properly tensioned per RCSC Table 8.1?
-
Is the appropriate feeler gage refused entry in at least half of the spaces between the protrusions?
-
Are the DTI protrusions facing away from the connecting plies?
-
(Snug-Tight) Have the plies of the connected elements been brought into firm contact as described in RCSC?
-
(Snug-Tight) Have the bolt assemblies been tightened sufficiently to prevent the turning of the nuts without use of a wrench?
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines
-
Specify Bolt Inspection Type
-
Comments/Description
-
Picture(s)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Location(s)/Grid Lines of deficiency(ies).
-
Location(s)/Grid Lines of deficiency(ies).
-
Weld Category
- Beam Connections
- Joist Connections
- Column Baseplates
- Vertical Bracing
- Miscellaneous Connections
- Moment Connections (Visual)
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Type of fasteners used at supporting steel.
- Arc Spot Welds ("Puddle Welds")
- Mechanical Fasteners
-
Does the visual quality and placement of the arc spot welds comply with the contract drawings and AWS D1.3 (2018), Section 8.1.1?
-
Describe the arc spot weld deficiency(ies).
- Incorrect weld spacing
- Undersized welds
- Incomplete fusion to decking
- Insufficient weld reinforcement (Underfill)
- Other (Please Specify)
-
Required Weld Pattern/Spacing
- 36/3
- 36/4
- 36/5
- 36/7
- 36/10
- 36/14
- 24/4
- 6" On Center
- 8" On Center
- 9" On Center
- 10" On Center
- 12" On Center
- 18" On Center
- 24" On Center
- Other (Please Specify)
-
Please specify the required weld pattern/spacing.
-
Installed Weld Pattern/Spacing
- 36/3
- 36/4
- 36/5
- 36/7
- 36/10
- 36/14
- 24/4
- 6" On Center
- 8" On Center
- 9" On Center
- 10" On Center
- 12" On Center
- 18" On Center
- 24" On Center
- Other (Please Specify)
-
Please specify the installed weld pattern/spacing.
-
Type of Mechanical Fasteners
-
Hilti Fastener Type
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing
- Insufficient penetration
- Excessive penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid lines of deficiency(ies).
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing
- Insufficient penetration
- Excessive penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid lines of deficiency(ies).
-
Describe the type of Hilti fastener.
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing
- Insufficient penetration
- Excessive penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid lines of deficiency(ies).
-
Type of Simpson Strong-Tie Fastener.
- Strong-Drive Self-Drilling X Metal Screw
- Strong-Drive XM Medium Head Metal Screw
- Other
-
Describe the type of Simpson Strong-Tie Fastener.
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Specify type of mechanical fastener.
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Description of the connection type(s)
-
Does the installation of the connection(s) comply with the contract drawings, manufacturer's recommendations, applicable code section?
-
Description of the deficiency.
-
Location(s)/Grid Lines of the deficiency(ies).
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Do the installed conditions comply with the contract drawings, AWS D1.1, AISC, and ACI requirements?
-
Please specify the type of deficiency(ies).
- Loose connection(s)
- Field enlarged baseplate bolt holes (torch-cut)
- Insufficient nut engagement with anchor rod (short anchor)
- Washers not installed
- Nuts not installed
- Incorrect washer grade
- Incorrect nut grade
- Other
- Missing welds at washers
-
Please specify type of deficiency(ies).
-
Location(s)/Grid Lines of deficiency(ies).
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Any other Item(s)/Area(s) inspected?
Inspection Item 8
-
Inspection Type
- Column Anchor Rods
- Bolted Connections
- Welded Connections
- Deck Fasteners
- Post-Installed Anchors
- Miscellaneous
-
Type of Bolt(s)
- High-Strength Bolts (Beam/Column Connections)
- Other (Please Specify)
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines
-
Comments/Description
-
Picture(s)
-
Do the bolt assemblies comply with RCSC requirements?
-
Description of deficiency(ies)
- Incorrect Grade - Bolt
- Incorrect Grade - Nut
- Incorrect Grade - Washer
-
Specify grade of bolts installed.
- Grade 5
- Grade 8
- ASTM A307
- Other
-
Please specify
-
Specify grade of installed nuts
-
Specify grade of installed washers.
-
Location(s)/Grid Lines of deficiency(ies)
-
Do the bolt assemblies comply with project requirements?
-
Description of deficiency(ies)
- Field-enlarged holes
- Incorrect bolt grade
- Not properly tightened
- Missing bolts assemblies
- Missing washers
- Missing nuts
- Incorrect bolt size
- Incorrect bolt length
- Incorrect washer grade
- Incorrect washer size
- Incorrect nut grade
- Incorrect nut size
- Other (please specify)
-
Please specify
-
Location(s)/Grid Lines of deficiency(ies)
-
Required bolt tensioning method.
- Snug-Tight Conditions
- Pretensioned
-
Method of pretensioning used
- Tension Control Bolts
- Turn-of-Nut
- Calibrated Torque Wrench
- Direct Tension Indicators (DTI)
-
Have the twist-off splines been correctly severed?
-
Have the bolt assemblies been properly match-marked and turned per RCSC Table 8.2?
-
Have the bolt assemblies been properly tensioned per RCSC Table 8.1?
-
Is the appropriate feeler gage refused entry in at least half of the spaces between the protrusions?
-
Are the DTI protrusions facing away from the connecting plies?
-
(Snug-Tight) Have the plies of the connected elements been brought into firm contact as described in RCSC?
-
(Snug-Tight) Have the bolt assemblies been tightened sufficiently to prevent the turning of the nuts without use of a wrench?
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines
-
Specify Bolt Inspection Type
-
Comments/Description
-
Picture(s)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Location(s)/Grid Lines of deficiency(ies).
-
Location(s)/Grid Lines of deficiency(ies).
-
Weld Category
- Beam Connections
- Joist Connections
- Column Baseplates
- Vertical Bracing
- Miscellaneous Connections
- Moment Connections (Visual)
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Type of fasteners used at supporting steel.
- Arc Spot Welds ("Puddle Welds")
- Mechanical Fasteners
-
Does the visual quality and placement of the arc spot welds comply with the contract drawings and AWS D1.3 (2018), Section 8.1.1?
-
Describe the arc spot weld deficiency(ies).
- Incorrect weld spacing
- Undersized welds
- Incomplete fusion to decking
- Insufficient weld reinforcement (Underfill)
- Other (Please Specify)
-
Required Weld Pattern/Spacing
- 36/3
- 36/4
- 36/5
- 36/7
- 36/10
- 36/14
- 24/4
- 6" On Center
- 8" On Center
- 9" On Center
- 10" On Center
- 12" On Center
- 18" On Center
- 24" On Center
- Other (Please Specify)
-
Please specify the required weld pattern/spacing.
-
Installed Weld Pattern/Spacing
- 36/3
- 36/4
- 36/5
- 36/7
- 36/10
- 36/14
- 24/4
- 6" On Center
- 8" On Center
- 9" On Center
- 10" On Center
- 12" On Center
- 18" On Center
- 24" On Center
- Other (Please Specify)
-
Please specify the installed weld pattern/spacing.
-
Type of Mechanical Fasteners
-
Hilti Fastener Type
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing
- Insufficient penetration
- Excessive penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid lines of deficiency(ies).
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing
- Insufficient penetration
- Excessive penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid lines of deficiency(ies).
-
Describe the type of Hilti fastener.
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing
- Insufficient penetration
- Excessive penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid lines of deficiency(ies).
-
Type of Simpson Strong-Tie Fastener.
- Strong-Drive Self-Drilling X Metal Screw
- Strong-Drive XM Medium Head Metal Screw
- Other
-
Describe the type of Simpson Strong-Tie Fastener.
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Specify type of mechanical fastener.
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Description of the connection type(s)
-
Does the installation of the connection(s) comply with the contract drawings, manufacturer's recommendations, applicable code section?
-
Description of the deficiency.
-
Location(s)/Grid Lines of the deficiency(ies).
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Do the installed conditions comply with the contract drawings, AWS D1.1, AISC, and ACI requirements?
-
Please specify the type of deficiency(ies).
- Loose connection(s)
- Field enlarged baseplate bolt holes (torch-cut)
- Insufficient nut engagement with anchor rod (short anchor)
- Washers not installed
- Nuts not installed
- Incorrect washer grade
- Incorrect nut grade
- Other
- Missing welds at washers
-
Please specify type of deficiency(ies).
-
Location(s)/Grid Lines of deficiency(ies).
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Any other Item(s)/Area(s) inspected?
Inspection Item 9
-
Inspection Type
- Column Anchor Rods
- Bolted Connections
- Welded Connections
- Deck Fasteners
- Post-Installed Anchors
- Miscellaneous
-
Type of Bolt(s)
- High-Strength Bolts (Beam/Column Connections)
- Other (Please Specify)
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines
-
Comments/Description
-
Picture(s)
-
Do the bolt assemblies comply with RCSC requirements?
-
Description of deficiency(ies)
- Incorrect Grade - Bolt
- Incorrect Grade - Nut
- Incorrect Grade - Washer
-
Specify grade of bolts installed.
- Grade 5
- Grade 8
- ASTM A307
- Other
-
Please specify
-
Specify grade of installed nuts
-
Specify grade of installed washers.
-
Location(s)/Grid Lines of deficiency(ies)
-
Do the bolt assemblies comply with project requirements?
-
Description of deficiency(ies)
- Field-enlarged holes
- Incorrect bolt grade
- Not properly tightened
- Missing bolts assemblies
- Missing washers
- Missing nuts
- Incorrect bolt size
- Incorrect bolt length
- Incorrect washer grade
- Incorrect washer size
- Incorrect nut grade
- Incorrect nut size
- Other (please specify)
-
Please specify
-
Location(s)/Grid Lines of deficiency(ies)
-
Required bolt tensioning method.
- Snug-Tight Conditions
- Pretensioned
-
Method of pretensioning used
- Tension Control Bolts
- Turn-of-Nut
- Calibrated Torque Wrench
- Direct Tension Indicators (DTI)
-
Have the twist-off splines been correctly severed?
-
Have the bolt assemblies been properly match-marked and turned per RCSC Table 8.2?
-
Have the bolt assemblies been properly tensioned per RCSC Table 8.1?
-
Is the appropriate feeler gage refused entry in at least half of the spaces between the protrusions?
-
Are the DTI protrusions facing away from the connecting plies?
-
(Snug-Tight) Have the plies of the connected elements been brought into firm contact as described in RCSC?
-
(Snug-Tight) Have the bolt assemblies been tightened sufficiently to prevent the turning of the nuts without use of a wrench?
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines
-
Specify Bolt Inspection Type
-
Comments/Description
-
Picture(s)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Location(s)/Grid Lines of deficiency(ies).
-
Location(s)/Grid Lines of deficiency(ies).
-
Weld Category
- Beam Connections
- Joist Connections
- Column Baseplates
- Vertical Bracing
- Miscellaneous Connections
- Moment Connections (Visual)
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Type of fasteners used at supporting steel.
- Arc Spot Welds ("Puddle Welds")
- Mechanical Fasteners
-
Does the visual quality and placement of the arc spot welds comply with the contract drawings and AWS D1.3 (2018), Section 8.1.1?
-
Describe the arc spot weld deficiency(ies).
- Incorrect weld spacing
- Undersized welds
- Incomplete fusion to decking
- Insufficient weld reinforcement (Underfill)
- Other (Please Specify)
-
Required Weld Pattern/Spacing
- 36/3
- 36/4
- 36/5
- 36/7
- 36/10
- 36/14
- 24/4
- 6" On Center
- 8" On Center
- 9" On Center
- 10" On Center
- 12" On Center
- 18" On Center
- 24" On Center
- Other (Please Specify)
-
Please specify the required weld pattern/spacing.
-
Installed Weld Pattern/Spacing
- 36/3
- 36/4
- 36/5
- 36/7
- 36/10
- 36/14
- 24/4
- 6" On Center
- 8" On Center
- 9" On Center
- 10" On Center
- 12" On Center
- 18" On Center
- 24" On Center
- Other (Please Specify)
-
Please specify the installed weld pattern/spacing.
-
Type of Mechanical Fasteners
-
Hilti Fastener Type
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing
- Insufficient penetration
- Excessive penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid lines of deficiency(ies).
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing
- Insufficient penetration
- Excessive penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid lines of deficiency(ies).
-
Describe the type of Hilti fastener.
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing
- Insufficient penetration
- Excessive penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid lines of deficiency(ies).
-
Type of Simpson Strong-Tie Fastener.
- Strong-Drive Self-Drilling X Metal Screw
- Strong-Drive XM Medium Head Metal Screw
- Other
-
Describe the type of Simpson Strong-Tie Fastener.
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Specify type of mechanical fastener.
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Description of the connection type(s)
-
Does the installation of the connection(s) comply with the contract drawings, manufacturer's recommendations, applicable code section?
-
Description of the deficiency.
-
Location(s)/Grid Lines of the deficiency(ies).
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Do the installed conditions comply with the contract drawings, AWS D1.1, AISC, and ACI requirements?
-
Please specify the type of deficiency(ies).
- Loose connection(s)
- Field enlarged baseplate bolt holes (torch-cut)
- Insufficient nut engagement with anchor rod (short anchor)
- Washers not installed
- Nuts not installed
- Incorrect washer grade
- Incorrect nut grade
- Other
- Missing welds at washers
-
Please specify type of deficiency(ies).
-
Location(s)/Grid Lines of deficiency(ies).
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Any other Item(s)/Area(s) inspected?
Inspection Item 10
-
Inspection Type
- Column Anchor Rods
- Bolted Connections
- Welded Connections
- Deck Fasteners
- Post-Installed Anchors
- Miscellaneous
-
Type of Bolt(s)
- High-Strength Bolts (Beam/Column Connections)
- Other (Please Specify)
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines
-
Comments/Description
-
Picture(s)
-
Do the bolt assemblies comply with RCSC requirements?
-
Description of deficiency(ies)
- Incorrect Grade - Bolt
- Incorrect Grade - Nut
- Incorrect Grade - Washer
-
Specify grade of bolts installed.
- Grade 5
- Grade 8
- ASTM A307
- Other
-
Please specify
-
Specify grade of installed nuts
-
Specify grade of installed washers.
-
Location(s)/Grid Lines of deficiency(ies)
-
Do the bolt assemblies comply with project requirements?
-
Description of deficiency(ies)
- Field-enlarged holes
- Incorrect bolt grade
- Not properly tightened
- Missing bolts assemblies
- Missing washers
- Missing nuts
- Incorrect bolt size
- Incorrect bolt length
- Incorrect washer grade
- Incorrect washer size
- Incorrect nut grade
- Incorrect nut size
- Other (please specify)
-
Please specify
-
Location(s)/Grid Lines of deficiency(ies)
-
Required bolt tensioning method.
- Snug-Tight Conditions
- Pretensioned
-
Method of pretensioning used
- Tension Control Bolts
- Turn-of-Nut
- Calibrated Torque Wrench
- Direct Tension Indicators (DTI)
-
Have the twist-off splines been correctly severed?
-
Have the bolt assemblies been properly match-marked and turned per RCSC Table 8.2?
-
Have the bolt assemblies been properly tensioned per RCSC Table 8.1?
-
Is the appropriate feeler gage refused entry in at least half of the spaces between the protrusions?
-
Are the DTI protrusions facing away from the connecting plies?
-
(Snug-Tight) Have the plies of the connected elements been brought into firm contact as described in RCSC?
-
(Snug-Tight) Have the bolt assemblies been tightened sufficiently to prevent the turning of the nuts without use of a wrench?
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines
-
Specify Bolt Inspection Type
-
Comments/Description
-
Picture(s)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Location(s)/Grid Lines of deficiency(ies).
-
Location(s)/Grid Lines of deficiency(ies).
-
Weld Category
- Beam Connections
- Joist Connections
- Column Baseplates
- Vertical Bracing
- Miscellaneous Connections
- Moment Connections (Visual)
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Does the visual quality of the welds comply with the specified details, contract drawings, and AWS D1.1 (2020), Table 8.1?
-
Describe the weld deficiencies (Select all that apply).
- Welds not cleaned (Slag not removed)
- Excessive Weld Undercut
- Weld Overlap
- Excessive Weld Porosity
- Undersized Fillet Welds
- Unfilled Weld Craters
- Lack of Fusion
- Missing Welds
- Insufficient Weld Length
- Welds Coated with Paint
- Excessive Weld Spacing
- Other (Please Specify)
-
Please specify.
-
Location(s)/Grid Lines of deficiency(ies)
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Type of fasteners used at supporting steel.
- Arc Spot Welds ("Puddle Welds")
- Mechanical Fasteners
-
Does the visual quality and placement of the arc spot welds comply with the contract drawings and AWS D1.3 (2018), Section 8.1.1?
-
Describe the arc spot weld deficiency(ies).
- Incorrect weld spacing
- Undersized welds
- Incomplete fusion to decking
- Insufficient weld reinforcement (Underfill)
- Other (Please Specify)
-
Required Weld Pattern/Spacing
- 36/3
- 36/4
- 36/5
- 36/7
- 36/10
- 36/14
- 24/4
- 6" On Center
- 8" On Center
- 9" On Center
- 10" On Center
- 12" On Center
- 18" On Center
- 24" On Center
- Other (Please Specify)
-
Please specify the required weld pattern/spacing.
-
Installed Weld Pattern/Spacing
- 36/3
- 36/4
- 36/5
- 36/7
- 36/10
- 36/14
- 24/4
- 6" On Center
- 8" On Center
- 9" On Center
- 10" On Center
- 12" On Center
- 18" On Center
- 24" On Center
- Other (Please Specify)
-
Please specify the installed weld pattern/spacing.
-
Type of Mechanical Fasteners
-
Hilti Fastener Type
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing
- Insufficient penetration
- Excessive penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid lines of deficiency(ies).
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing
- Insufficient penetration
- Excessive penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid lines of deficiency(ies).
-
Describe the type of Hilti fastener.
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing
- Insufficient penetration
- Excessive penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid lines of deficiency(ies).
-
Type of Simpson Strong-Tie Fastener.
- Strong-Drive Self-Drilling X Metal Screw
- Strong-Drive XM Medium Head Metal Screw
- Other
-
Describe the type of Simpson Strong-Tie Fastener.
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Specify type of mechanical fastener.
-
Are the fasteners at supporting steel installed correctly per the contract drawings, manufacturer's recommendations, and SDI requirements?
-
Describe the deficiency(ies).
- Missing fasteners
- Incorrect fastener pattern/spacing.
- Insufficient penetration
- Other
-
Describe the deficiency(ies)
-
Location(s)/Grid Lines of deficiencies (approximate).
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Description of the connection type(s)
-
Does the installation of the connection(s) comply with the contract drawings, manufacturer's recommendations, applicable code section?
-
Description of the deficiency.
-
Location(s)/Grid Lines of the deficiency(ies).
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Area/Building/Section
-
Floor Level and/or Elevation
-
Grid Lines Inspected
-
Referenced Details (if available)
-
Comments/Description
-
Picture(s)
-
Do the installed conditions comply with the contract drawings, AWS D1.1, AISC, and ACI requirements?
-
Please specify the type of deficiency(ies).
- Loose connection(s)
- Field enlarged baseplate bolt holes (torch-cut)
- Insufficient nut engagement with anchor rod (short anchor)
- Washers not installed
- Nuts not installed
- Incorrect washer grade
- Incorrect nut grade
- Other
- Missing welds at washers
-
Please specify type of deficiency(ies).
-
Location(s)/Grid Lines of deficiency(ies).
-
Accept/Reject
- Compliant
- Non-Compliant
- RFI Needed
- N/A
-
Any other Item(s)/Area(s) inspected?