Information

  • Document No.

  • Audit Title

  • Client / Site

  • Conducted on

  • Prepared by

  • Location
  • Personnel

  • Customer Service Area

  • Price Range Catagory

  • Viscore/ Job Number

  • Responsible Manager

  • Auditee

  • Company

7 Exchange Equipment

  • 7.001 Equipment positioned & installed correctly, ventilation unimpeded

  • 7.002 Equipment anchored / mounted compliant with seismic needs

  • 7.003 Equip secure; Fastenings, Isolation, Earthing, Masking, Covers

  • 7.004 Equipment & racks labelled correctly. Node name visible. TLRD system name visible.

  • 7.005 Static straps fitted where required

  • 7.006 Alarms connected & tested. Commissioning info confirmed

  • 7.007 DF components secure, labelled, jumper management correct

  • 7.008 Conduits and pipework adequately routed & anchored

  • 7.009 Cable tray earthing & isolation correct

  • 7.01 Cable type & size and labelled OK. Installation neat and tidy

  • 7.011 Cable and jumper terminations tidy & to required standard

  • 7.012 UTP cables are supported and routed securely

  • 7.013 Structured Cabling supported and routed securely, not tight bends, Velcro ties used

  • 7.014 Circuit breakers / fuses correct type & size & labelled

  • 7.015 Equipment area tidy, task waste removed

  • 7.016 Air conditioning functioning and temperature OK

  • 7.017 Trunking manages fibre cords within maximum capacity limits; drop off position OK, flexitube anchored at equip, fibre slack managed.

  • 7.018 Fire & Smoke stopping around wall cable access holes

8 UCLL CoLocation

  • 8.001 Customer owned copper / fibre cables labelled every metre with owner name

  • 8.002 Fibre cable tails coiled on top of Customer footprint or feed direct into footprint (no excess)

  • 8.003 Trunking manages fibre cords within maximum capacity limits; drop off position OK, flexitube anchored at equip

  • 8.004 Customer equipment secured compliant to seismic standards

  • 8.005 MDF cabling installation & testing confirmed

  • 8.006 50 Volt End Of Row feeds clearly labelled for each Customer

  • 8.007 Customer equipment earthed (6mm cable green sheath) connected to Telecom earth bar

  • 8.008 NetMAP, Floor and Rack Layout & Record Systems represent Customer information correctly

  • 8.009 Previous QA and/or Build activity completed, no outstanding actions

11 OFDF & Exchange Fibre

  • 11.001 All optical cables 100% support on horizontal & managed on vertical

  • 11.002 OFDF hardware secure: OFDF Drawer-Cable Trough-Guides-Rack

  • 11.003 Network labelling correct at OFDF (OFDF Designation, Jumper to/from label)

  • 11.004 Optical cables & cords adequately managed within racks and shelves

  • 11.005 OFDF Single Fibre Organiser not overfilled (<1.5mtr tails)

  • 11.006 Fibre splicing within design tolerance

  • 11.007 30mm bending radius unconditionally observed at all locations

  • 11.008 Fibre pigtail label records 'from' OFDF ID and SFO number

  • 11.009 Trunking manages fibre cords within maximum capacity limits; drop off position OK, flexitube anchored at equip

  • 11.01 Protective caps on all unterminated connectors

  • 11.012 Laser Safety labels (1M Safety) at OFDF (inside and front panel)

  • 11.013 No fibre task waste on site, all optical (glass) ends safely contained (H&S)

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.