Title Page

  • Site conducted

  • Conducted on

  • Prepared by

  • CFL declaration- AA 2242 certifies that waste water has been tested and treated IAW DAWE tables 6 and 7 of Biosecurity Approved Arrangement Site requirements (4.3 cleaning) and is Biosecurity Cleared for Disposal

  • Signature of AA N2242 Biosecurity Representative

  • Register Number

Testing Results

  • Test start date/time

Test pH range (must be 5.0 to 7.0)

  • Within guidance of 5.0 to 7.0? Treat 150g of Dry Acid to bring down 1 level if not, add actions in notes

  • Re Test pH Level

  • pH level between 5.0 and 7.0

Treatment

  • Hypochlorite date of manufacturing within 2 years

  • Add 14.4L (15L container) of Hypochlorite to Tank

Agitate for 10 Minutes

  • Start Time

  • End Time

Test Free Chlorine Level

  • What is the High Chlorine test level

  • Chlorine Level 200 ppm or higher

Retain 1 hour

  • Start Time

  • End Time

Free Chlorine Level

  • Is Free Chlorine 5 ppm or greater

  • Water Treatment met all requirements and water to be cleared and disposed

Disposal Records

  • Pumped into Tanker

  • Tanker Cell Number

  • Discharged at Morpeth

  • Morpeth Consignment Number

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.