Water Temperature Checks - Sentinel Points
-
Site - Hampton By Hilton Sheffield
-
Conducted on
-
Prepared by
-
Location
Water Temp. Checks
-
Water Temperature Tests: Hot & Cold running water provided to all outlets must be maintained at temperatures which ensure that hygiene and health & safety requirements are met.
Hot Must be above 50°C, but below 60°C - Cold Must be below 20°C Testing Procedure : The Maintenance team should test temperatures at sentinel points including furthest from source, closest to source, and a few outlets in between. All water tank temperatures must be recorded. Mains Water Supply temperature into the hotel must be recorded. Record findings on this Monthly Sentinel Hot & Cold Water Temperatures audit. Temperature check should be carried out after continuously running water through the outlet for 1 minute for both hot and cold services. Records of these temperatures should be kept and filed by the Hotel Manager or Maintenance Manager and be available for inspection as required by an authorized body.
Water source location (Repeat this section in accordance with the number of tests you do in line with your WRA requirements)
-
Location
-
Hot Water Temperature
-
Cold Water Temperature
-
Outlet Condition
Random Outlets
-
Location
-
Hot Water
-
Cold Water
-
Outlet Condition
Calorifier Flow & Return Temperatures
-
Location / Number
-
Hot Water Flow Temperature
-
Hot Water Return Temperature
-
Calorifier condition
Signature
-
Name