Brick tie channels
-
Main Contractor:
-
Project Number:
-
Issued to:
-
QA Sheet No:
-
Elevation:
-
Level:
-
Comments:
STRUCTURE
-
SFS area + QA complete.
-
Personnel
- Installer
- A2O
Tyvek, K15 + Ancon brick tie channels
-
Tyvek Housewrap installed horizontally with joints taped using Tyvek tape. Overlap of 100mm horizontally and 150 vertically. Any tears / rips repaired with 100mm overlap.
-
Personnel
- Installer
- A2O
-
K 15 50mm insulation installed using 10nr fixings per full board. 8nr plastic washers and 2nr fire rated metal washers per full board.
-
Personnel
-
All joints of K15 taped using silver tape at least 75mm wide.
-
Personnel
- Installer
- A2O
-
Ancon brick tie channels installed using ancon supplied fixings at 600mm centres (SFS stud locations) into SFS studs at 450mm centres vertically
-
Personnel
Additional / bespoke items
-
Additional / bespoke items