AIM fire barriers
-
Main Contractor:
-
Project Number:
-
Issued to:
-
QA Sheet No:
-
Elevation:
-
Level:
-
Comments:
Fire barrier checks
-
Clips must penetrate barrier by minimum of 50%
-
Personnel
- Installer
- A2O
-
Clips to be at maximum 500mm centres.
-
Personnel
- Installer
- A2O
-
Clips to be mid depth (top to bottom)
-
Personnel
- Installer
- A2O
-
Check polythene layer is not compromised.
-
Personnel
- Installer
- A2O
-
Intumescent edge to face outwards.
-
Personnel
- Installer
- A2O
-
Any gaps to be sealed with intumescent sealant if required.
-
Personnel
- Installer
- A2O
-
Airspace should not exceed 44mm.
-