    1. Answer "Checked" or "Hold" for the questions below, then identify the personnel who conducted the checking.
    2. Add photos and notes by clicking on the paperclip icon.
    3. To add a Corrective Measure click on the paperclip icon, then "Add Action", provide a description, assign to a member, set priority and due date.
    4. Complete audit by providing digital signature.
    5. Share your report by exporting as PDF, Word, Excel or Web Link

AIM fire barriers

  • Main Contractor:

  • Project Number:

  • Issued to:

  • QA Sheet No:

  • Elevation:

  • Level:

  • Comments:

Fire barrier checks

  • Clips must penetrate barrier by minimum of 50%

  • Personnel

  • Clips to be at maximum 500mm centres.

  • Personnel

  • Clips to be mid depth (top to bottom)

  • Personnel

  • Check polythene layer is not compromised.

  • Personnel

  • Intumescent edge to face outwards.

  • Personnel

  • Any gaps to be sealed with intumescent sealant if required.

  • Personnel

  • Airspace should not exceed 44mm.

  • Personnel

Completion

  • Installer Signature:

  • A2O Signature:

  • Client Signature:

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.