Title Page

  • Site conducted

  • Audit Title

  • Project Name

  • Conducted on

  • Prepared by

  • Location
  • Instructions
    -------------------
    1. Answer "Checked" or "Hold" for the questions below, then identify the personnel who conducted the checking.
    2. Add photos and notes by clicking on the paperclip icon.
    3. To add a Corrective Measure click on the paperclip icon, then "Add Action", provide a description, assign to a member, set priority and due date.
    4. Complete audit by providing digital signature.
    5. Share your report by exporting as PDF, Word, Excel or Web Link

A2O - Composite roof-lights

  • Main Contractor:

  • Project Number:

  • Issued to:

  • QA Sheet No:

  • Elevation:

  • Level:

  • Comments:

Existing sheets

  • All existing mastic cleaned from remaining roof sheets

  • Personnel

Rooflight over panel endlap detail

  • 50mm x 8mm butyl tape with PE foam co laminate centre applied 10mm from the top edge of the KS100RW sheet.<br>

  • Personnel

  • 4no. Poppy red stainless steel self drilling self-tapping primary fixings with minimum 16mm diameter non-ferrous EPDM backed washer. 9no. KR-VRT-SS-30 poppy red 6.3mm diameter x 30mm long stainless steel stitching screw with 19mm diameter washer.

  • All fixings to be in line 30mm up from the edge of the rooflight cutback

Rooflight over rooflight lap detail

  • 50mm x 8mm butyl tape with PE foam co laminate centre applied 10mm from the top edge of the KS1000RW sheet.

  • Personnel

  • 40no. Poppy red stainless steel self-drilling self-tapping primary fixings with minimum 16mm diameter non-ferrous EPDM backed washer, complete with 35 x 23 storm washers

  • Personnel

  • Factory applied stiching plate

  • Personnel

  • 6no. KR-VRT-SS-30 poppy red 6.3mm diameter x 30mm long stainless steel stitching screw with 19mm diameter washer. 2 per valley

  • Personnel

  • All fixings to be in line 30mm up from the edge of the rooflight cutback

  • Personnel

Panel over rooflight end lap detail

  • 50mm x 8mm butyl tape with PE foam co laminate centre applied 10mm from the top edge of the KS1000RW sheet.

  • Personnel

  • 4no. Poppy red stainless steel self-drilling self-tapping primary fixings with minimum 16mm diameter non-ferrous EPDm backed washer, complete with 35 x 23 storm washers.

  • Personnel

  • Factory applied stitching plate

  • Personnel

  • 6 no. KR-VRT-SS-30 poppy red 6.3mm diameter x 30mm long stainless steel stitching screw with 19mm diameter washer. 2 per valley.

  • Personnel

  • All fixings to be in line 30mm up from the edge of the rooflight cutback

Intermediate rooflight fixing detail

  • Rooflights to be fixed at every purlin location with 4no. Poppy red stainless steel self-drilling self-tapping primary fixings with minimum 16mm diameter non-ferrous EPDM backed washer, complete with 35 x 23mm storm washers at crown locations to intermediate rails

Side lap details

  • Kingspan FAWS side lap sealant or site applied butyl

  • 6 x 5mm butyl rubber sealant applied in continuous unbroken length at sidelap to weather side of stitching screws

  • 50mm polyband applied in continuous unbroken length to seal existing stitcher fixing holes

  • Install side lap cover cap to side lap of KS1000RW

  • Side laps to be stitched at maximum 300mm centres with poppy red stainless steel stitcher screws 6.3mm diameter x 30mm long with 19mm washer

Completion

  • Installer Signature:

  • A2O Signature:

  • Client Signature:

  • undefined

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.