Client / Site: Barwon Water - Black Rock WRP Inlet Works Upgrade 400 Black Rock Connewarre
-
Inspection Area:
-
Reference: BW Technical Specification Rev 0 Clause: 38.12 Flexible Conduits 38.20 Mechanical Protection 38.21 Equipment Mounting 38.25 Earthing
-
Document No. CA-CS-010 ITP No:
VISUAL CHECKLIST
-
316 stainless steel conduit used
-
All supports, brackets, saddles and clips spaced so that no appreciable sag occurs in such conduits and cables
-
Segregation of dissimilar metals using 3mm insulating spacers
-
Fixings using galvanised bolts, nuts and washers shall be installed at spacings that ensure that the runs remain straight and in every case the distance between such fixings shall not exceed one metre
-
Holes shall be drilled through the flanges of RSJ's channels or any steel structure
-
Flexible metallic conduits shall be complete with oil tight waterproof end fittings
-
Flexible PVC hose shall be used to enclose building wire between ridged PVC or metallic conduit and final devices
-
Segregation between power and instrument wiring maintained
-
Sheet metal covers constructed of minimum 14 gauge galvanised steel material
-
Sheet metal covers installed top revise mechanical protection of equipment shall be constructed so as to totally enclose such electrical equipment and associated conduits and or cables
-
Sheet metal covers installed to provide mechanical protection of conduits and or cable shall be free of burrs and sharp edges
-
PVC sheathed flexible metallic conduit shall be used for final connections to plant devices subject to vibration or where mechanical protection is required
-
All terminal number from 01 upwards
-
Wiring numbers clearly identified by ferrules
-
A sufficient length of flexible conduit and cable shall be positioned and mounted where applicable to permit the positional adjustment of equipment without electrical disconnection or same, as for example, for adjustment no - flow limit switches and the likes
-
Screw in hose fittings shall be used to terminate the PVC hose at the conduit and final device
-
All burrs removed and screwed bushes fitted to ends
-
Metal conduits shall be earthed to the electrical enclosure they originate from or to metal structure that is earthed
-
Notes/Comments
APPROVALS
-
Conduit system is:
-
Actions to be taken:
-
Entered on Punch List
-
Punch list Reference Number:
-
Item No:
-
Person Completing the Checklist
- Greg Grima
- John Toner
- Shane Dando
- David Howard
-
Signature:
-
Agfab Approval By:
- Greg Grima
- John Toner
- Shane Dando
- David Howard
-
Signature: