Building Inspection - Reinforcement / Steel
-
Conducted on:
-
Prepared by:
-
Address:
-
Construction Certificate / Complying Development Certificate Number:
-
Inspection Notes:
-
Check configuration of the slab matches the approved plans?
-
Check for correct orientation.
-
Damp proofing material is a high impact grade polyethylene film and is branded as such?
-
Damp proofing film lapped 200mm and is it tape sealed?
-
Penetrations to the damp proofing material sleeved and sealed?
-
Are beams within the slab the correct size?
-
Are beams bedded into solid natural ground or controlled fill as designed by the engineer?
-
Is correct reinforcing material being used?
-
Is correct coverage of reinforcement maintained?
-
Re-entrant reinforcement placed at all inward facing corners.
-
Are edge rebates a minimum of 20mm in depth?
-
Check exterior masonry will not over hang in excess of 15mm.
-
If the edge exceeds 150mm in depth, is the minimum width of the edge beam at the base of the rebate more than 200mm?