Vertical Siderise Firebarrier
-
Main Contractor:
-
Project Number:
-
Issued to:
-
QA Sheet No:
-
Elevation:
-
Level:
-
Comments:
Siderise fire barrier materials
-
Fire barrier schedule is available<br>within the site documentation
-
Personnel
- Installer
- A2O
-
Fire barrier materials have been<br>checked on delivery to site to be<br>correct type and specification in<br>accordance with the A2O fire barrier<br>schedule
-
Personnel
-
Fire barrier materials have been<br>stored on site in an appropriate<br>manned in accordance with<br>manufacturers recommendation.<br>"Keep material in original packaging<br>until it is to be used. Store material<br>to protect against<br>damage including the weather"
-
Personnel
-
All fire barrier brackets, fixings and<br>tape has been delivered to site and<br>checked that they are in accordance<br>with the A2O fire barrier schedule<br>and manufacturers specification.
-
Personnel
Pre-installation
-
A site meeting with fire barrier<br>supplier [Siderise] arranged and<br>carried out in advance of installation<br>works commencing. To include any<br>training that may be required.
-
Personnel
- Installer
- A2O
-
A2O Fire barrier construction<br>drawing are on site within the A2O<br>drawing file.
-
Personnel
- Installer
- A2O
-
All installation operatives have been<br>briefed on the specific installation of<br>the fire barriers to be installed, in<br>accordance with manufacturers<br>recommendation
-
Personnel
Fire barrier installation
-
Check fire barrier locations are in<br>accordance with A2O fire barrier<br>setting out construction drawings.
-
Personnel
- Installer
- A2O
-
At each fire barrier location, check<br>that thickness of fire barrier is in<br>accordance with cavity void plus<br>compression allowance in<br>accordance with the manufacturers<br>specification.
-
Personnel
- Installer
- A2O
-
If the fire barrier to be installed<br>requires to be cut to size, make sure<br>that the cut allows for the extra size<br>to ensure the required compression<br>and be sure to cut in the direction<br>that is marked on the foil facing to<br>maintain compression in accordance<br>with manufacturers specification.
-
Personnel
- Installer
- A2O
-
Manually fold the installation<br>brackets to allow the correct<br>embedment into the fire barrier. This<br>needs to be 75% of the depth of the<br>fire bracket to ensure a compression<br>zone within each barrier, i.e. if the<br>cut fire barrier is 100mm, the bracket<br>would penetrate the barrier 75mm.
-
Personnel
- Installer
- A2O
-
Bracket fixings are fixed at 600mm<br>centres with non combustible fixings<br>[no plastic or rubber washers].<br>Ensure fixings are as per A2O or<br>manufacturers specification.
-
Personnel
- Installer
- A2O
-
Ensure that the fire barrier is tightly<br>abutted to the barriers to each side<br>and seal the joints with RFT 120 x 45<br>foil tape.
-
Personnel
- Installer
- A2O
-
Arrange inspection by Siderise before commencing with any further cladding finishes.
-
On completion of inspection, cavity<br>fire barriers are to be signed off by a<br>Siderise approved qualified person.
-
Personnel
- Installer
- A2O
Completion
-
Installer Signature:
-
A2O Signature:
-
Client Signature: