Description of Location
Safety/Housekeeping
-
Scrap material picked up
-
Proper PPE being worn-Face shields required if shooting into concrete or cutting
-
Ladders-Not on top 2 rungs, hips and thighs within ladder
Materials
-
Manual Pull Stations - Notifier NBG-12LX
-
Addressable Thermal Detector - FST-851A- Off White 6"
-
Horns/Strobes - Notifier <br>-Indoor Ceiling Horn/Strobe - White 6.8" diameter<br>-Indoor Ceiling Strobe - White 6.8" diameter<br>-Indoor Wall Horn/Strobe - Red 5x5.5"<br>-Indoor Wall Horn - White 5x5.5"<br>-Outdoor wall/ceiling strobe - Red
-
Speaker Strobes - Notifier (Red speaker strobes, white speakers only) Wall- 6"x5", ceiling 7" diameter
-
FA Wire=Copper
-
Installed work is protected from damage
Installation
-
Fire alarm cabling is supported independently of all other systems.
-
Fire alarm wiring shall be in conduit in concealed, non-accessible, or exposed areas. Plenum rated cable in concealed accessible areas
-
FA cable/conduit adequately supported. Zip ties are not allowed for conduit.
-
Minimum conduit size is 3/4"
-
Verify colored conduit fittings used as follows:<br>Black-normal<br>Blue-standby<br>Orange-mechanical<br>Yellow-life safety<br>Green-grounding<br>Red-fire alarm<br>White-security<br>No paint-comm
-
EMT installed at exterior locations
-
No liquid tight flex conduit
-
Fire alarm wiring only within raceways
-
FA conduit/cable is not resting on other materials
-
Flex connectors for all devices mounted in ACT
-
No wire nut connections allowed
-
FA conduit/cable is installed with building lines
-
Smoke/heat detectors are 12" from light fixtures
-
Detectors are installed within 3' of ceiling elevation change per NFPA 72E
-
Pull boxes must have base 4' AFF and be within 5' from a door
-
All devices mounted are mounted to the ceiling where possible
-
Devices are centered in ceiling tiles
-
Raceways 6" away from parallel runs of flues/hot water pipes
-
Devices are on full tiles, not partial tiles
-
Wall mount alarms at 80" AFF or 6" below ceiling (whichever is lower)
-
Locate devices in ACT where possible, not gyp
-
All conductors in pull boxes or cabinets with more than one wire must be labeled
-
Paint conduit to match adjacent finishes in exposed areas. <br>
-
Surface mounted boxes (pull stations) should be painted the same color as the alarm station.
-
FA conduit/cable does not obstruct access to VAVs (3' clearance required)
-
Plenum rated cable ties/anchors
-
FA boxes and covers are red and identified
-
Grommets or bushings for fire alarm provided at conduit stub out
-
Smoke/heat detectors are free of paint
VESDA
-
VESDA piping supported at 5' centers
-
Max distance between testing points = 20'
-
Pipe shall be orange, identified w/ Aspirating Smoke Detector Pipe, w/ stickers on sampling points
Required Testing
-
Ground Resistance
-
Dielectric strength and insulation resistance
-
Smoke and Thermal Sensor Tests-Voltage activation sensitivity testing
-
Field Inspection Test of each device
Misc.
-
Contractor drawings are current set with applicable changes posted
-
Photos attached
-
BIM drawings attached
-
Details attached
-
Incomplete items moved to QUIT log?
-