Title Page
-
Cut-out change assessment
-
ENWL training academy
-
Conducted on
-
John lee and Martin Meyrick
-
Personnel
Jointing
2c PILC COMPOUND FILLED live cut-out change (plastic cut-out only) X1 and SNE cut-out change x1
-
PILC cutout change overall result
-
SNE cutout change overall result
-
Correct PPE worn throughout?
-
Polarity test done before cutout changed
-
ELI test done before cutout change
-
Old cutout removed safely
-
Cutout kit fitted as per the correct module
-
Plumb removed safely
-
Earth fitted as per correct module
-
New cutout fitted correctly, series 5 or 6
-
Polarity test done correctly
-
ELI test done correctly
Service position tests
Polarity and ELI testing
-
CNE cut-out correct polarity found?
-
CNE cut-out no neutral found?
-
CNE cut-out cross polarity found?
-
CNE cut-out dead found?
-
SNE cut-out correct polarity found?
-
SNE cut-out cross polarity found?
-
SNE cut-out No neutral found?
-
SNE cut-out DEAD found?
-
Correct ELI reading for CNE cut-out identified (max reading 0.35 Ohms)?
-
Correct ELI reading for SNE cut-out identified (max reading 0.80 Ohms)?
Signatures
Course review
-
Assessor name
-
Assessor name
-