Title Page

  • Module 1 service jointing

  • ENWL training academy

  • Conducted on

  • John lee

  • Personnel

Service to service jointing

Service to service jointing

  • CNE single phase cut-out

  • Plastic service bottle end

  • CNE single phase breech joint

  • CNE single phase breech joint

  • CNE single phase live cut and straight joint

  • CNE single phase live cut and straight joint

  • SNE single phase live cut and straight joint

  • SNE single phase live cut and straight joint

  • SNE single phase breech joint

  • SNE single phase breech joint

  • CNE 3 phase breech joint

  • CNE 3 phase breech joint

  • CNE 3 phase live cut and straight joint

  • CNE 3 phase live cut and straight joint

  • SCNE 3 phase live cut and straight joint

  • SCNE 3 phase live cut and straight joint

  • 2c 35mm SNE breech joint to 2c 35mm PILC

  • 2c 35mm SNE breech joint to 2c 35mm PILC

  • 2c 35mm PILC live cut and straight joint to 2c 35mm SNE

  • 2c 35mm PILC live cut and straight joint to 2c 35mm SNE

  • 2c 4mm CNE live cut and straight joint

  • 2c 4mm CNE live cut and straight joint

Service to mains jointing

Service to mains jointing

  • Single phase CNE breech to 4c PILC main

  • Single phase SNE breech to 4c PILC main

  • 3 phase CNE breech to 4c PILC main

  • Single phase CNE breech to Consac main

  • 3 phase SNE breech to 4c PILC main

  • Single phase CNE breech to Consac main

  • 3 phase CNE breech to Consac main

  • Single phase CNE breech to 3c Waveform main

  • 3 phase CNE breech to Consac main

  • 3 phase CNE breech to 3c Waveform main

  • Single phase SNE breech to 4c Waveform main (connect to Blue phase)

  • Single phase SNE breech to 4c Waveform main (connect to Blue phase)

Test joints

Test Joints

  • Test joint 1

  • Test joint 2

  • Test joint 3

  • Test joint 4

  • Test joint 5

Service position tests

Polarity and ELI testing

  • CNE cut-out correct polarity found?

  • CNE cut-out no neutral found?

  • CNE cut-out cross polarity found?

  • CNE cut-out dead found?

  • SNE cut-out correct polarity found?

  • SNE cut-out cross polarity found?

  • SNE cut-out No neutral found?

  • SNE cut-out DEAD found?

  • Correct ELI reading for CNE cut-out identified (max reading 0.35 Ohms)?

  • Correct ELI reading for SNE cut-out identified (max reading 0.80 Ohms)?

Fault finding on 4c waveform

Testing on 4c mains cable

  • Phase down found?

  • Healthy cable found?

  • No neutral found?

  • No earth found?

  • Phase and neutral cross found?

  • Cable dead found?

  • Phase to phase (weld) found?

Insulation resistance and continuity

Insulation resistance and continuity testing on 3c 25mm CNE

  • Did they find short between 2 phases?

  • Did they find the cable healthy?

  • Did they find broken phase?

Insulation resistance and continuity testing 3 x single phase 35mm CNE cables

  • Were the 2 healthy cables found?

  • Was the cable with the dead short found?

Signatures

  • Summary

Signatures

  • Trainers signature

  • Trainees signature

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.