Inspect date on test tag
-
Attach photo of tag
-
Date of last test
-
Inspect condition of lead
-
Inspect condition of extraction hose
-
Inspect the damper flap on the extractor hood
-
Check the fan inlet guard is tight and secure
-
Test the airflow rate at a distance of 150mm from the face of the LEV system inlet, with hot wire anemometer, and confirmed not less than 0.5 meters per second
-
Documented on WHS plan ( refer ES000711R100)
-
Replace filter element where required or if contaminated (results in insufficient airflow rate available at inlet of fume extractor hose
-
Check the tension on the fume extractor casing locks, check to confirm adequate sealing of the air filter casing achieved. Eccentric air filter casing locks adjusted where required to achieve effective sealing.
-