Are Flash back arrestors installed at the regulator and hand piece on both the Oxygen and Acetylene lines?
-
Are the Flashback arrestors marked with the date they are to be removed or put into service? Note arrestors shall be replaced every 12 months, some departments may have a ZPM#3 and change on a set day within the department, confirm process if date not sighted.
-
Are there signs of discoloration near Flash back Arrestors? (inspect hose and knobs on handpiece)
-
Is the Oxygen Gauge pressure reading 200kpa and Acetylene Gauge reading 75 Kpa? (if gauge not working, remove from service, designated pressures stated above, if reading above reduce regulator flow)
-
Is the Oxygen Gauge and Acetylene contents gauge working? (if not working, remove from service)
-
Are both regulators color-coded? RED & BLACK
-
Are the hoses approved for use? red for Acetylene, blue for Oxygen, rated & approved for use
-
Are all connections tightened firmly with wrench?
-
Are the fittings connected to the hose approved eg factory crimped/screwed fittings? (remove if hose clamp or crimp is used)
-
Do the hoses show any signs of cracking/deformation/burns that can impact on hose integrity?
-
Does the equipment have any oil or grease evidence? (highly combustible)
-
Has the cutting tip been inspected and in good order?
-
Conduct leak detection of hoses fittings, torch valves, and tip to confirm no leaks are present on the unit being inspected?
-