Information
-
Document No.
-
Client / Site
-
Conducted on
-
Prepared by
-
Location
-
Is this an Intrusive or non-intrusive Inspection
-
Fire Door Inspection
Fire Door
Door Location
-
Location
-
Add Image of door
-
Door Manufacturer Known
-
Certification Label Present
- FD30
- FD60
- FD90
- FD120
- None Present
-
Add Image of Label
-
Is Door Data Available
Door
-
Door Type
- Timber Flush / Panelled
- Timber Glazed
- Joinery Flush / Pannelled
- Joinery Glazed
- Composite Flush /Panelled
- Composite Glazed
- Metal Flush
- Glazed Metal
-
Single or Double Leaf
-
Door Width
-
Door Height
-
Door Thickness
-
Door Width Leaf 1
-
Door Height Leaf 1
-
Door Thickness Leaf 1
-
Door Width Leaf 2
-
Door Height Leaf 2
-
Door Thickness Leaf 2
-
Does the door leaf sit against the door stop and is it free from distortion?
-
If the door is veneered or lipped, is the glue still holding these products firmly in place?
-
Fire signage
- Automatic Fire Door Keep Clear
- Keep Locked Shut
- Fire Door Keep Shut
- Fire Exit
- Push to Open
- None Present
Door Frame
-
Door Frame Type
-
Is the frame in a good state of repair?
-
Is the door frame securely attached to the wall?
- Frame fixings visible
- Distance between fixings (as per data)
- Frame fixings hidden
-
If a planted door stop is present, is it firmly attached?
Perimeter Gaps (mm)
-
What gap at head of door
-
What gap at hinged edge of door
-
What gap at closing edge of door
-
What gap at joining edge (Double Doors)
-
Are door leaf to frame gaps compliant
-
Is there a consistent gap under the door that allows it to swing without touching the floor covering?
-
Is the door to floor covering gap consistently 10mm (3mm if smoke seals are fitted) or less when the door is closed?
-
If the door leaf is fitted with a threshold seal, does the seal make contact with the floor covering when the door is closed?
-
Is the threshold gap compliant
Door Seals
-
Are intumescent seals in place?
-
What seal size is installed
- FD30 - 10 x 2mm
- FD30 - 10 x 4mm
- FD30 - 15 x 2mm
- FD30 - 15 x 4mm
- FD30 - Other
- FD60 - 15 x 4mm
- Other
-
Are the seals well attached inside the groove in the door leaf or frame?
-
Are brush or fin seals combined with the intumescent
-
Are brush or fin type seals free from damage?
-
Are separate smoke / acoustic seals attached
-
Are the smoke seals continuous around the door leaf or door frame?
Door Hinges
-
Are hinges CE / UKCA marked
-
Type of hinge
-
Are Hinges Positioned Correctly
- As per Test Evidence
- In Line with Industry Standard (150-200mm top of door to centre of hinge, 200-250mm base of door to centre of hinge
-
Is there a minimum of 3 hinges with all the screws fitted?
-
Are all the screws the correct size?
-
Are the hinges packed
Door Closers
-
Is a closer required
-
Is a door closer Installed
-
Type of closer
-
Is the door closer CE / UKCA Marked
-
Open the door to 75mm or 5 degress. Does it close and engage with the latch
-
Is the closer securely attached to the frame
-
Is the closer free from damage
-
If unlatched does the closer hold the door in line with the frame and intumescent seals
-
If hung in pairs, do they close in-line if both are opened and released together
-
If hold open device is used, is it electronically released
-
Does the hold open device release the door when required
Lock, Latch and Hardware
-
Does the latch hold the door firmly in the frame without rattling
-
Is Panic / Emergency Set Installed
-
Is the lock CE / UKCA Marked
-
Hardware
- Kick Plate
- Door Viewer
- Flush Bolts
- Surface Bolts
- Air Transfer Grille
- Edge / Face Protectors
- Pull Handle
Glazing & Glass
-
Is the door glazed
-
Is the glass marked as per EN14449 or EN 572: 3 or 6 or EN 1748-2-2 or EN 13024 or EN 14179 or EN 12150
-
Is the intumescent seal continuous and attached to the glass and bead?
-
Are the glazing beads well attached to the frame and free from damage?
-
Is the glass free from cracking or damage
-
If the glass has been replaced is it fire rated glass?
Compliance
-
Compliance Rating
Priorty Rating
-
Action required