Title Page

  • Which call Point is being checked?

  • Conducted on

  • Prepared by

  • Location

Weekly Test

  • Go to a manual call point unit and firmly press the black dot in the Centre on the call point, the sounders will start.

  • Use the white reset key to reset the unit

  • Go to the control panel, turn the key to enable controls

  • Press silence/sound alarm to stop the sounders

  • Press Reset

  • Anything to report/comments

Unknown Activation - Checks

  • Make sure There is no fire.

  • Go to the control panel and the display will show the fire location and a zone LED will be lit.

  • At the control panel, turn the key to enable controls and press the silence/sounds alarm.

  • Investigate the area/zone which has caused the activation.

  • Check all manual call point units within the zone, to make sure the glass has not been damaged.

  • Check all smoke/heat detectors within the zone, the detector which has caused the activation will have a red light illuminated on it.

  • Once you are certain that there is no fire, press the reset button.

  • If a detector has gone off for no reason, report the fault to render alarms on 01642 230696.

  • Document the activation in your fire alarm log book.

  • Any Comments

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.