Title Page
-
Store Number
-
Store Name
-
Conducted on
-
Prepared by
Packs
-
Are there any Packs on site?
-
Check all compressor running to operational temperatures and pressures
-
Test low level switches are operational
-
Position level sensors and mark level indicators if possible
Condensers/Gas Coolers
-
Does the Condenser have sufficient space for air flow around it?
-
Please provide photo of restrictions
-
Are Condensers Clean
-
Please provide photos of clean condensers
-
Check air flow across coil with Anemometer
-
Clean condensers
-
Please provide reason why these have not been cleaned
-
Check air flow across coil with Anemometer
-
Please provide photos of condensers before and after being cleaned
-
Check fans are operational and rotation is correct
Inverters
-
Are there any inverters on site?
-
Are all inverters operational and free from faults (including fans and clean heat sinks)
Cold rooms
-
Are there any Coldstores onsite?
-
Are the coldstores integral or on condensing units?
-
Is there Sufficient airflow ventilation around the unit. If not please provide Photograph of location.
-
Please provide evidence of issue
-
Is the condenser Clean
-
Clean condenser
-
Please Provide reasons why condenser is not being cleaned
-
Are there Door switches fitted?
-
Does the door switch work?
-
Please repair or arrange replacement
-
Check all cold store doors are operating correctly
-
Check all internal door flaps are working correctly and free from damage
-
Check trim heaters are working
-
Check all fans are working and rotation is correct
Back of House Integrals
-
Are there any williams integral cabinets on site
-
Do all doors close correctly?
-
Check all Williams condensers are clean
-
Please provide photos of clean condensers
-
Clean Williams condensers
-
Please provide reason why these have not been cleaned
-
Please provide photos of condensers before and after being cleaned
Shop Floor Cabinets
-
Is Airflow acceptable on all cabinets
-
Please investigate and rectify
-
Check all frozen trim heaters are operational
-
Are there condensate pump trays on site
-
Please Clean trays
-
Are there any signs of water leaks on shop floor
Shop floor integrals
-
Are there any Integral cabinets on the shopfloor
-
Check all integral condensers are clean
-
Please provide photos of clean condensers
-
Clean Integral condensers
-
Please provide reason why these have not been cleaned
-
Please provide photos of condensers before and after being cleaned
Air Conditioning/Ventilation
-
Are all airconditioning filters clean?
-
Clean Filters
-
please provide reasons why
-
Is there any ventilation blowing directly into cabinets?
-
Please rectify this if unable please list why and inform Managing engineer
Networking
-
Check that all fixtures are online.
Additional works needed
-
Any further works or parts needed
-
Please contact service solution desk if any further works are required, or if work orders need to be raised.
-
Email this form to your Manager and the TA Team