Title Page
-
Site conducted
-
Conducted on
-
Prepared by
-
Plot
Carpentry
Carpentry
Stairs
-
Are stairs are fitted correctly with strings cut shorter
-
Are Newel posts plumb
-
Is nosing fitted level with equal overhang
-
Timber down centre of stairs for tacking
-
4x1 running up exterior side of string to allow for boarders
-
Ensure stair tread winders are supported
-
Ensure stairwell fall protection in place including kick plate
-
Ensure tread and newel protection in place
Walls
-
Butrace wall stud work to be 400 centres
-
Ensure all plasterboard catchers are fitted
-
Ensure all stud work on ground floor has dpc underneath sole plate
-
Pattresses to be fitted 800 high for radiators, toilets, basins, towel rails, boilers and pigs ear.
-
Pattresses to kitchen units 150mm ply 800 and 2.1 high
-
Ensure all svp boxings are plumb and square
-
Ensure attic trap is trimmed with double noggins around perimeter and frame out with 4x1 25mm down
-
Ensure all noggings are in place
Plumbing
-
Protective plate installed to gas pipe
-
Hot and cold water feeds clipped with correct colours
-
Hot water pipes lagged where touching pipes and zip tied or taped
-
Waste pipe supported through floor and laid to fall
-
Soil pipes suitable clipped
-
Where soil pipe goes through ceiling sealed
-
Soil pipe connected to vent or durgo
-
All Soil pipes to be mechanically fixed in roof space
-
All pipe work in studs foiled tape both sides
-
All pipework left under pressure
-
All Core Holes Cut
-
All Holes to external envelope sealed
-
All open ends to pipes capped
-
Where pipe work goes through bulkheads to airing cupboards to be mastic
Electrical
-
Protective plate installed to tales
-
Boxes 75mm Spaced apart
-
Light switches 200mm away froma Architrave
-
Lights and smoke alarms 300mm away from sprinklers
-
Ducting supported and not sagging in any areas
-
Ducting sealed penetrating wall
-
Correct size clips used
-
All cables clipped 225mm apart
-
All Extras have been put in
-
All Sockets in correct position as per drawing
-
All gromets to be fitted where required
Roof
-
Vents in correct postion
-
Felt free from tears
-
Fire proofing installed to gables and soffits
-
Ridge line knifed for ventilation
Windows
-
Window opening 450mm where fire escape required
-
Are escape windows no more than 1100mm from the floor
-
Are windows level with even margins
-
Straps facing down to window frame
-
2 fixings to each strap
-
All windows foamed with no gaps
-
Are trickle vents in correct rooms
General
-
Insulation around watermain
-
Plot left Tidy
-
All membrane lapped to prevent air leakage and free from tears
-
Name