The following page starts the inspection. Every question relates to something Bierce has pulled us up on. Please ensure everything is checked properly.
Inside Inspection
-
Is there background ventilation in all habitable rooms? (photos required) *Background ventilation window trickle vents or wall vents
-
Is there dMEVs in all wet rooms, are they fully sleeved and are they all operational (photos required) Wet rooms: Bathroom, Kitchen, Utility Room and WC
-
Do all habitable door undercuts have at least 7-10mm clearance?
-
Is there a core vent in place if there is a back boiler or gas fire? (photo required)
-
Have you ensured any sub floor ventilation remains open? (usually sub floor vents if the oven sits on the floor)
Underfloor Inspection
-
Has the home got sufficient access (at least 1 hatch per side of the axle)
-
Is there adequate ventilation under the park home? (1 air brick/vent on each long end, 2 air bricks/vents on each short end)
-
Is there sufficient jacks supporting the chassis and are they in good condition (photos required) 8 for a single, 16 for a double
-
Have all water-feed pipes been lagged?
-
Is the system fully sealed & battened to ensure no cold bridging (photos required)
-
Have you ensured that you have not covered up a gas pipe
-
If any gas pipes are running underneath between the joists, have you ensured you have cut ventilation into the system