Ceiling Inspection- Reference AS/NZ 2589

  • Deviation of Timber and Steel framing does not exceed 5mm over 1.8m

  • Moisture content in timber framing at time of installation does not exceed 15%

  • End of Furring Channels have 10mm clearance from wall face

  • Control Joints formed correctly as required by design

  • Correct fixing method used (FAFAFAF) ceiling sheets 1200mm wide

  • correct application of adhesive used 25mm diameter

  • Back blocking of Butt joints 400mm min width and 50mm min overlap at recessed joints

  • Back blocking is neatly cut and buttered together within 50mm of joists / support members

  • A minimum of 10mm of cornice cement has been applied to the back edge of the cornice

  • Joints are not overbuilt with jointing compound that exceeds 2mm over the width of the joint being 250mm

  • All jointing compound is finished evenly and free from tool marks and ridges

  • Cornice line does not deviate more than 4mm over a length of 2m

  • No visible blemishes in finish of ceiling joins- Pitted areas, drag lines from sanding ,

Wall Lining Inspection - reference to AS/NZ 2589

  • All masonry surface must be free of efflorescence , dust, oils, paints or any substance that will impair the bonding of the adhesive

  • Masonry walls do not exceed 3m in height

  • Masonry walls are plumb within 10mm

  • Masonry Adhesive has been applied to the wall or back of board at maximum 450mm centres

  • Masonry adhesive has been applied to walls 50mm from edges

  • Masonry adhesive to wet areas applied at 200mm centres

  • Plasterboard lining has a minimum 6mm gap at base of walls

  • All jointing and cement jointing compound is finished evenly and free from tool marks and ridges

  • internal corners are treated with joint cement and are no less than 75mm either side of the corner

  • joint build up to internal corners does not exceed 2mm

  • external corners are treated with jointing cement and are no less than 250mm either side of the corner

  • joint build up at external angles /corners does not exceed 3mm

  • joints to walls are not overbuilt by no more than 2mm above the surface

  • no visible gouges, scratches, voids or pock marks in the jointing cement

  • joint edges are not oversanded resulting in scuffing of the paper surface

  • corner beads are plumb at straight

  • All rubbish placed in and/or next to bin and weighted down

  • All excess adhesive / cement compound cleaned off door frames, windows and slab

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.